NetworX Series
™
NX-6 CONTROL PANEL
Installation and Startup
Page 1: ...NetworX Series NX 6 CONTROL PANEL Installation and Startup ...
Page 2: ...ument contains proprietary information of GE Security and is furnished to its customer solely to assist that customer in the installation testing operations and or maintenance of the equipment described This document shall not be reproduced in whole or in part nor shall its contents be disclosed to any third party without the written approval of GE Security Please refer to the current GE Security ...
Page 3: ...XILIARY OUTPUT EVENT SELECTION 22 NX 6 PROGRAMMING WORKSHEETS 29 COMMUNICATOR CODES FOR SLOW SPEED FORMATS ONLY 33 APPENDIX 1 REPORTING FIXED CODES IN CONTACT ID AND SIA 37 APPENDIX 2 REPORTING ZONE CODES IN SIA OR CONTACT ID 38 APPENDIX 3 EXPANDER NUMBERS FOR REPORTING EXPANDER TROUBLE 39 NX 6 WIRING DIAGRAM 40 TERMINAL DESCRIPTION 41 BOARD INSTALLATION 42 REGULATORY NOTICES 43 LOCAL TELEPHONE CO...
Page 4: ...omatically selected when Zone 7 is programmed as a AFire Zone Type Refer to the Standard Zone Type chart on page 18 If Zone 7 is used as wireless AFire zone the resistor must be placed on the 2 wire smoke loop See diagram and terminal descriptions on pages 40 and 41 Part Description NX 6 KIT Includes NX 6 Control NX 108E LED Keypad 16 5V 40VA Transformer NX 6 NX 6 Control Only NX 108E 8 Zone LED K...
Page 5: ...utes of inactivity until the next Aopening time loc 52 or until the system is armed The 45 minute timer will be extended when there is activity in the building causing the Ready LED to turn off and on The Auto Arming of a partition can be programmed to be silent If closing reports are sent the user code will be 97 Loc 23 and 52 55 pg 17 and 23 Automatic Bypass Instant Arming When enabled the contr...
Page 6: ...ee different phone numbers for dual split or multiple reports selectable by event or partition Loc 4 10 and 16 pg 12 15 Duress Code If a duress code is programmed the NX 6 will send a duress signal whenever the panel is armed or disarmed with this code If open close reports are sent the user code will be 254 Loc 44 pg 21 Dynamic Battery Test The NX 6 can be programmed to perform a Dynamic Battery ...
Page 7: ...All reportable events report to the log Keypad Activated Panics The NX 6 has three keypad activated panics that will send reports to the central station Auxiliary 1 Fire Auxiliary 2 Medical and Keypad Panic Auxiliary 1 will activate the steady Fire siren Auxiliary 2 will sound the keypad and the Keypad Panic can be programmed to be silent or audible sound siren Loc 23 pg 17 Keypad Sounder Control ...
Page 8: ... exit delay or when the central station receiver acknowledges the closing report It can also give one blast for remote keyswitch arming and two blasts for remote disarming Loc 37 pg 19 Siren Supervision The NX 6 has a ASiren Supervision circuit that will constantly monitor the siren on the NX 6 and can be programmed to report if the wires are cut Loc 37 pg 19 Silent Exit Option The exit delay can ...
Page 9: ...one test where all zones become silent and local non reporting Each time a zone is faulted the zone light on the LED keypad will illuminate and the chime will sound The number of the faulted zone s will be displayed on the LCD keypad It will also be entered into alarm memory and the internal log To exit at any time during this mode enter a user code Otherwise the AWalk Test Mode will automatically...
Page 10: ...d zones when the system is armed 6 Enable Panic Fire Medical Beeptone will sound a short beep to verify that the keypress was accepted 7 Suppresses the Service LED will not allow the Service LED to illuminate for any reason If there is a system trouble pressing r 2 will still show the Service menu NOTE For UL installations the Service LED shall not be suppressed 8 Enable multi partition viewing en...
Page 11: ... 7 will use the chart to the right 8 If this LED is off LEDs 1 7 use the chart to the left Step 3 Enter r The Instant LED will illuminate steady This moves you to the partition enable which tells the system what partition this user can arm disarm Step 4 LEDs 1 2 illuminate for each partition that the user has authorization for To change any of these numbers press 1 2 to permit or deny access to th...
Page 12: ...eady to enter another programming location If an attempt is made to program an invalid entry for a particular segment the keypad sounder will emit a triple error beep beep beep beep and remain in that segment awaiting a valid entry EXITING THE PROGRAM MODE When all the desired changes in programming have been made press the Exit key to exit this programming level and go to the Select a Module To P...
Page 13: ...hout changing the data in the current segment PROGRAMMING EXAMPLE FIGURE 2 Feature Selection Data Location 23 Segment 1 1 Quick Arm 2 Re Exit 3 Auto Bypass 4 Silent Keypad Panic 5 Audible Keypad Panic 6 Keypad Auxiliary 1 7 Keypad Auxiliary 2 8 Multi Keypad Tamper Press the key on the numeric keypad that corresponds to the feature you wish to enable disable When an LED is on a feature is enabled w...
Page 14: ... will automatically enroll the devices The enrolling process takes about 12 seconds during which time the Service LED will illuminate User codes will not be accepted during the enrolling process If a speaker is attached to the NX 6 it will click at this time If a siren or bell is attached to the NX 6 it will sound for about 1 second Once a module is enrolled if it is not detected by the control th...
Page 15: ...1800hz transmit 2300hz handshake double round parity 40 p p s hex capability 8 3 1 or 4 1 fast 1800hz transmit 1400hz handshake double round parity 40 p p s hex capability 9 3 1 or 4 1 fast with parity 1800hz transmit 2300hz handshake single round w parity 40 p p s hex capability 10 3 1 or 4 1 fast with parity 1800hz transmit 1400hz handshake single round w parity 40 p p s hex capability 11 4 2 ex...
Page 16: ...it of the account code If the account code is 6 digits long program all 6 segments If this location is left unprogrammed account code 1 will be used when the second phone number is dialed LOCATION 8 COMMUNICATOR FORMAT FOR PHONE 2 1 segment numerical data Location 8 contains the communicator format used to transmit to the receiver connected to Phone 2 Consult the instruction manual for your centra...
Page 17: ...ntains the communicator format used to transmit to the receiver connected to phone 3 Consult the instruction manual for your central station receiver to determine which format is compatible and select from the 15 formats listed on page 13 If you require a format other than those listed review the override options described in Location 18 to build the appropriate format A 15 must be programmed in l...
Page 18: ...ult is 8 and the NX 6 will answer on 8 rings LOCATION 21 DOWNLOAD CONTROL 1 segment feature selection Location 21 contains the feature selections for the controlling of download sessions The following features can be enabled or disabled using this location See the feature definitions beginning on page 3 â On enables two call answering machine defeat ã On enables tone sniff answering machine defeat...
Page 19: ... enables the Zone Bypassed Sounder Alert feature å On enables the AC Power Low Battery Sounder Alert feature æ On enables Bypass toggle ç On enables Silent Auto Arm è On enables the Automatic Instant feature é Reserved Segment 3 â On enables Opening and Closing reports ã On enables Zone Bypass reporting ä On enables Zone Restore reporting å On enables Zone Trouble reporting æ On enables Zone Tampe...
Page 20: ...ONE ENABLED This zone will be instant when the system is armed and no entry or exit delay is being timed It is delayed during entry and exit delay times If a Cross Zone is not being timed it will start a Cross Zone timer If a Cross Zone is being timed it will create an instant alarm This zone will automatically bypass when enabled in Segment 1 of Location 23 13 INSTANT ENTRY GUARD This zone create...
Page 21: ...e armed A zone that resides in more than 1 partition will be reported to its lowest partition Location 28 has 8 segments Segment 1 corresponds to zone 9 and Segment 8 corresponds to zone 16 Segments 1 8 â Partition 1 ã Partition 2 LOCATION 37 SIREN AND SYSTEM SUPERVISION 5 segments feature selection Location 37 is used to enable various system feature and reporting options Refer to the feature def...
Page 22: ... keypad sounds for zone and box tampers è Reserved é On if keypad sounds for expander trouble required for UL installations LOCATION 40 SYSTEM TIMERS 10 segments numerical data Location 40 contains the duration of various system timing functions Example If you desire the duration of the Dynamic Battery Test to be 30 minutes you should program 3 0 r in segment 1 of this location The 3 0 is the numb...
Page 23: ...nables Go To Program Code as an arm disarm code ç On enables Go To Program Code to bypass zones è On enables Go To Program Code opening and closing reports é Reserved Segment 2 â On enables the Go To Program Code for Partition 1 ã On enables the Go To Program Code for Partition 2 LOCATION 44 DURESS CODE 6 segments numerical data Location 44 contains the Duress code This Location contains either 4 ...
Page 24: ...put follow the event AUXILIARY OUTPUT EVENT SELECTION Table 2 1 DATA EVENT DATA EVENT DATA EVENT 0 Burglary Alarm 19 Exit 38 Download In Process 1 Fire Alarm 20 Entry or Exit 39 Smoke Power 2 24 Hour Alarm 21 Armed State 40 Short Circuit Over current 3 Trouble Alarm 22 Disarmed State 41 Box Tamper 4 Tamper Alarm 23 Ready 42 Siren Tamper 5 Yelping Siren Burglary 24 Not Ready 43 Any Open 6 Temporal ...
Page 25: ...rlier than closing time for Auto Arm Aux Outputs or Code Authorization to function properly Segment 1 Program the hour of the closing auto arm time Segment 2 Program the minutes after the hour of the closing auto arm time LOCATION 54 DAYS OF WEEK EACH PARTITION IS OPEN 2 segments feature selection Location 54 selects which days of the week each partition is open On these days Aarm only after close...
Page 26: ...d as the ones digit of the zone number i e 9 for zone 9 Any segment left as 0 will follow the Segment 1 selection Segment 1 Partition 1 Trouble Code Segment 2 Partition 2 Trouble Code LOCATION 60 SENSOR LOW BATTERY 2 segments numerical data Location 60 contains the event code for a zone Sensor Low Battery for a 4 2 format The digit programmed in this location will be sent as the tens digit The zon...
Page 27: ...R OVER CURRENT RESTORE 4 segments numerical data Location 70 contains the tens and ones digits for a 4 2 format that will be sent if Aux Power Over current Reporting is enabled Segment 1 contains the tens digit of the Aux Power Over current Reporting Segment 2 contains the ones digit of the Aux Power Over current Reporting Segment 3 contains the tens digit of the Aux Power Over current Restore Seg...
Page 28: ... for a 4 2 format that will be sent if Recent Closing and or Exit Error Reporting is enabled Segment 1 contains the tens digit for the Recent Closing Reporting Segment 2 contains the digit for the Exit Error Reporting The ones digit is the ones digit of the user who closed If the user number is greater than 9 the numbers will begin repeating i e 9 for user 29 If it is required to report Recent Clo...
Page 29: ...f the account code is 6 digits long program all 6 segments LOCATION 90 PARTITION 2 FEATURES REPORTING ENABLE 3 segments feature selection Location 90 is used to enable certain features that can be accessed or are visible to the user from the keypad of the system In addition certain communicator reports are enabled in this location Each of these features can be enabled by partition This location co...
Page 30: ... should Automatically Bypass or Bypass for Stay Arming é Local only turn on if this zone should not be reported Segment 2 â On will beep the keypad for alarm ã On will sound the yelping siren for alarm ä On if zone type will sound the temporal siren for alarm å On if zone type will chime æ On if zone type can be bypassed ç On if zone type is included in the group shunt è On if zone type is force a...
Page 31: ... Reserved PHONE 1 SELECT WHICH PARTITIONS REPORT TO PHONE 1 5 14 1 Partition 1 2 Partition 2 6 14 PHONE 2 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ 7 14 PHONE 2 ACCOUNT CODE 10 10 10 10 10 10 __ __ __ __ __ __ 8 14 PHONE 2 REPORTING FORMAT 0 __ 9 14 PHONE 2 DIAL ATTEMPTS BACKUP CONTROL 8 0 __ __ PHONE 2 SELECT EVENTS TO ...
Page 32: ...own control panel 5 Lock out local programming 6 Lock out communicator programming 7 Lock out download section 8 Enables callback at autotest interval 22 16 CALLBACK PHONE NUMBER 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ FEATURE SELECTION PARTITION 1 23 17 Segment 1 1 Quick Arm 2 Re Exit 3 Auto Bypass 4 Silent Panic 5 Au...
Page 33: ... out Siren sounds for expander trouble required for U L Immediate restore by zone Dynamic battery test performed upon arming Battery missing test performed every 12 seconds Manual bell test performed during r 4 test function Manual communicator test performed during r 4 test function Box tamper enabled Segment 3 1 2 3 4 5 6 7 8 Box Tamper report enabled AC Fail report enabled Low Battery report en...
Page 34: ... PROGRAM CODE PARTITION AND AUTHORIZATION Segment 1 1 Reserved 2 Enables Go To Program Code as an arm only code 3 Enables Go To Program Code as an arm only after closing 4 Enables Go To Program Code as a master arm disarm code can change user codes 5 Enables Go To Program Code as an arm disarm code 6 Enables Go To Program Code to bypass zones 7 Enables Go To Program Code opening and closing report...
Page 35: ...NG TIME 52 23 Segment 1 Program the hour of the opening time Segment 2 Program the minutes after the hour of the opening time 8 0 ___ ___ CLOSING TIME AUTO ARMING TIME 53 23 Segment 1 Program the hour of the closing time auto arming time Segment 2 Program the minutes after hour of closing auto arming time 20 0 DAYS OF THE WEEK EACH PARTITION IS OPEN Segments 1 2 Partition 1 2 54 23 Sunday Monday T...
Page 36: ... __ OPENING COMMUNICATOR CODE 77 26 Segment 1 Partition 1 Opening Code Segment 2 Partition 2 Opening Code 0 0 __ __ CLOSING COMMUNICATOR CODE 78 26 Segment 1 Partition 1 Closing Code Segment 2 Partition 2 Closing Code 0 0 __ __ 79 26 AUTOTEST COMMUNICATOR CODE 0 0 __ __ 80 26 RECENT CLOSING AND EXIT ERROR 0 0 __ __ 81 26 START PROGRAMMING END PROGRAMMING 0 0 0 0 __ __ __ __ 82 26 END DOWNLOAD 0 0 ...
Page 37: ... PAGE 28 TO UNDERSTAND THESE DEFAULTS 112 28 ZONE TYPE 2 ALARM EVENT CODE 2 ____ 113 28 ZONE TYPE 2 CHARACTERISTIC SELECT 2 125 78 _____ _____ _____ 114 28 ZONE TYPE 3 ALARM EVENT CODE 7 ____ 115 28 ZONE TYPE 3 CHARACTERISTIC SELECT 5 1245 5678 _____ _____ _____ 116 28 ZONE TYPE 4 ALARM EVENT CODE 5 ____ 117 28 ZONE TYPE 4 CHARACTERISTIC SELECT 45 125 5678 _____ _____ _____ 118 28 ZONE TYPE 5 ALAR...
Page 38: ... _____ _____ _____ 140 28 ZONE TYPE 16 ALARM EVENT CODE 4 ____ 141 28 ZONE TYPE 16 CHARACTERISTIC SELECT 0 12456 5678 _____ _____ _____ 142 28 ZONE TYPE 17 ALARM EVENT CODE 7 ____ 143 28 ZONE TYPE 17 CHARACTERISTIC SELECT 5 1245 25678 _____ _____ _____ 144 28 ZONE TYPE 18 ALARM EVENT CODE 5 ____ 145 28 ZONE TYPE 18 CHARACTERISTIC SELECT 457 125 25678 _____ _____ _____ 146 28 ZONE TYPE 19 ALARM EVE...
Page 39: ...W BATTERY RESTORE device number 309 YR AC FAIL device number 301 AT AC RESTORE device number 301 AR BOX TAMPER device number 137 TA BOX TAMPER RESTORE device number 137 TR KEYPAD TAMPER 137 TA KEYPAD PANIC AUDIBLE 120 PA KEYPAD PANIC SILENT 121 HA DURESS 121 HA KEYPAD AUXILIARY 1 110 FA KEYPAD AUXILIARY 2 100 MA RF SENSOR LOST zone number 381 T RF SENSOR RESTORE zone number 381 R SENSOR LOW BATTER...
Page 40: ...Periodic Test 15 GA Gas Alarm 16 KA Heat Alarm 17 WA Water Alarm 18 QA Emergency Alarm 19 SA Sprinkler Alarm 20 ZA Freeze Alarm The NX 6 has the ability to report Ademco Contact ID transmissions Each report in Contact ID consists of an Event Code and a Zone ID The zone ID is the zone that created the alarm The event code will come from the chart below and be programmed in the Zone Type event code ...
Page 41: ...2 233 7 240 241 8 248 249 REMOTE POWER SUPPLY NX 320E OUTPUT MODULE NX 508E Address Dip Switch Setting Address Dip Switch Setting 84 All switches off 88 Switch 3 on 24 Switch 1 2 on 28 Switch 1 2 3 on 85 Switch 1 on 89 Switch 1 3 on 25 Switch 3 on 29 All switches off 86 Switch 2 on 90 Switch 2 3 on 26 Switch 1 3 on 30 Switch 1 on 87 Switch 1 2 on 91 All switches on 27 Switch 2 3 on 31 Switch 2 on ...
Page 42: ...Page 40 NX 6 WIRING DIAGRAM ...
Page 43: ...pt smoke detectors and keypads This terminal and KP POS are limited to 1 amp total current when added together ZONE 6 Connect to one side of zone 6 loop Connect the other side to com terminal Open or short causes alarm COM Common terminal for zones 5 6 ZONE 5 Connect to one side of zone 5 loop Connect the other side to COM terminal Open or short causes alarm ZONE 4 ZONE 1 Connect as described for ...
Page 44: ...ecurely Diagram 3 The PC Board should slide freely in the grooves of both guides K IMPORTANT 1 If separate power supplies are necessary to accommodate additional devices safety standards require that each power supply be prominently marked with adequate instructions for removing all power from the unit 2 Dispose of used batteries according to the manufacturer s instructions and or local government...
Page 45: ...m is with the device the customer shall discontinue use until it is repaired Equipment Information MANUFACTURER OF CONNECTING EQUIPMENT CADDX CONTROLS INC FCC REGISTRATION NUMBER GCQUSA 25950 AL E RINGER EQUIVALENCE 0 1 B The following applies to products which have the CE mark attached CE DECLARATION OF CONFORMITY Manufacturer s Name Caddx Controls Manufacturer s Address 1420 North Main St Gladew...
Page 46: ...sion is required For 24 hours of standby power using a 7 0 AH battery limit auxiliary power load to 140 mA For 24 hours of standby power using a 17 2 AH battery limit auxiliary power load to 400 mA The silent keypad option shall not be enabled UL has only verified compatibility with the following listed DACRs and formats Sure Gard SG MLR2 DG 2 9 10 12 13 14 Silent Knight 9000 2 12 FBI CP220FBI 13 ...
Page 47: ...ntry Delay s Entry 1 Delay 24 1 30 30 240 sec Entry 2 Delay 24 3 30 30 240 sec Abort Window for Non Fire Zones Dialer Delay 40 8 30 Enabled may be disabled by zone zone type Abort Window Time for Non Fire Zones Dialer Delay 40 8 30 15 45 sec NOTE Combined Abort window and Entry Delay must not exceed 1 minute Abort Annunciation This feature is non programmable in the panel Flashing Cancel LED goes ...
Page 48: ...NSE 500mS OPERATING TEMPERATURE 32 to 120 degrees F LED KEYPAD Current Draw 130 mA max Zones Normal w o Sounder 55 mA Dimensions 6 4 Wide 4 0 High 1 1 Deep NX 148E LCD KEYPAD Current Draw 110 mA max w o Sounder 75 mA Dimensions 6 4 Wide 5 3 High 1 0 Deep METAL ENCLOSURE DIMENSION 11 25 Wide 11 25 High 3 50 Deep SHIPPING WEIGHT 9 lbs Main 800 727 2339 Technical Support 888 437 3287 Outside the US 9...