Split Range Operation - 4700P/4800P
Split ranging permits the operation of two valves in sequence from one control instrument signal.
The total stroking of each valve occurs with one half the signal (i.e., 3-9 psig or 9-15 psig). The
following table shows, for example, the plug positions of two valves (both air to close action, open
on air failure operating in
split range
) with a 3-15 psig instrument signal.
Table 4: Split Range Operation
Instrument Signal
Air Signal to Close
No. 1
Valve Plug Position
(3-9 psig)
Air Signal to Close
No. 2
Valve Plug Position
(9-15 psig)
psig
mbar
3
207
Full Open
Full Open
6
414
Half Open
Full Open
9
620
Closed
Full Open
12
827
Closed
Half Open
15
1034
Closed
Closed