Installation must be in accordance with current applicable country codes and manufacturer’s in-
structions.
Maximum pressure 150 PSI.
Intrinsically
Safe
Installation must be in accordance with current editions of applicable
country codes, Figure 15 on page 42, and manufacturer’s instruc-
tions. Housing protection rating IP 66.
WARNING
Do not open when energized. Do not open when an explosive gas
atmosphere is present. Use cables rated to
5 °C above ambient.
For flameproof (Ex d protection concept):
The marking of the equipment shall include the following:
Sira 02ATEX1274
II 2GD
Ex d IIC T6 Gb
T
a
= -40 °C to +55 °C
Ex d IIC T5 Gb
T
a
= -40 °C to +70 °C
Ex d IIC T4 Gb
T
a
= -40 °C to +85 °C
Ex t IIIC T90 ° Db
T
a
= -40 °C to +55 °C
For intrinsically safe (Ex ia protection concept):
Sira 02ATEX2277X
II 1GD
Ex ia IIC T4 Ga
T
a
= -40 °C to +80 °C, P
i
= 1.1 W
Ex ia IIC T6 Ga
T
a
= -40 °C to +55 °C, P
i
= 0.33 W
Summary of Contents for Masoneilan 4700E
Page 4: ...This page intentionally left blank ...
Page 8: ...This page intentionally left blank ...
Page 10: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 40: ... 2015 General Electric Company All rights reserved 40 GE Oil Gas Figure 13 FM Installation ...
Page 42: ... 2015 General Electric Company All rights reserved 42 GE Oil Gas Figure 15 ATEX Installation ...
Page 46: ...This page intentionally left blank ...
Page 66: ... 2015 General Electric Company All rights reserved 66 GE Oil Gas ...
Page 78: ...This page intentionally left blank ...
Page 79: ......