Electrical Installation of 4700E/4800E
Electrical connections should be made as shown in Figure 12. The terminals will accept wire sizes
up to AWG 14.
The loop controller driving the positioner must be capable of supplying 4-20 mA with an output
voltage compliance of at least 5 VDC.
The available output voltage of a current source is reduced by loop wiring resistance. This can be
checked by connecting a resistor of value (250 Ohms + Loop Resistance) across the output of the
controller and verifying that at 100% controller output 20 mA is obtainable.
CAUTION
Do not use a voltage source to drive the positioner as it may
cause permanent damage.
CAUTION
The positioner must be installed in accordance with local and
national codes of practice in both general purpose and hazardous
area locations. The electrical components are fully isolated from
ground and therefore grounding is unnecessary for functional
purposes. Grounding may be necessary to conform to installation
codes.
The positioner is normally supplied with a 1/2" NPT conduit entry.
(M20 is optional) Internal and external ground terminals are
provided for use if grounding is required.
Summary of Contents for Masoneilan 4700E
Page 4: ...This page intentionally left blank ...
Page 8: ...This page intentionally left blank ...
Page 10: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 40: ... 2015 General Electric Company All rights reserved 40 GE Oil Gas Figure 13 FM Installation ...
Page 42: ... 2015 General Electric Company All rights reserved 42 GE Oil Gas Figure 15 ATEX Installation ...
Page 46: ...This page intentionally left blank ...
Page 66: ... 2015 General Electric Company All rights reserved 66 GE Oil Gas ...
Page 78: ...This page intentionally left blank ...
Page 79: ......