Critical Power
Modifications reserved
Page 63/69
GE_UPS_ISG_TLE_SUL_M62_1M0_2US_V010.docx
Installation Guide
TLE Series 625 - 750 - 1000 UL S2
5
CUSTOMER INTERFACE
Fig. 9-1 TLE Series 600 & 750 - Connectivity rack and Serial port J35µP – RS232
TLE Series 625 - 750 - 1000
has the following equipment’s:
-
Serial Port J35µP - RS232
(see
Section 5.1).
-
Customer Interface board
(see
Section 5.2).
-
Connectivity rack
ready for the installation of four connectivity boards.
Possible connectivity configurations with TLE Series 625 - 750 - 1000
Fig. 5-2 Connectivity Rack
For a
Single UPS
it’s possible to install the following
connectivity boards:
-
max. 3
“Customer Interface” boards
;
-
max. 2
“3-ph SNMP/WEB Plug-in Adapter” boards
.
For a
Parallel System
(max. 6 UPS) it’s possible to install
the following connectivity boards:
-
max. 3
“Customer Interface”
boards
for each UPS;
-
max. 2
“3-ph SNMP/WEB Plug-in Adapter” boards
for
Parallel System
.
ATTENTION !
The installation of any option board must be performed by
GE SERVICE
TECHNICIAN
.
Prior to the installation, connection and cabling of any option board the UPS
must be COMPLETELY POWERED DOWN and all the power sources that will be
connected to the option board must be DE-ENERGIZED.
Option board shall be connected only to Safety Extra Low Voltage circuits (SELV
for IEC-UL-CSA60950-1): voltage up to 30Vac / 42.4Vpk or 60Vdc maximum and
galvanically separated from AC Utility supply.
Keep SELV cables separated from HIGH VOLTAGE cables.
J35µP
- RS232
Connectivity rack
1
2
TLES
_UL
_75
0-1000
_S2
_UP
S co
nne
ctivi
ty_01
J35µP
- RS232
Connectivity
rack
J35µP
- RS232
Connectivity
rack
- +
1
2
Q1
0 OFF
I ON
- +
1
2
Q1
0 OFF
I ON
TLE Series 1000
TLE Series 625-750
TLES_UL_2
25-750_S1_
Connectivi
ty rack_01.
SNMP card
J3
J2
J5
J4
16
15
4
19
18
17
20
9
8
7
6
5
14
13
12
3
2
1
22
11
21
10