User Manual
TLE Scalable Series 40 - 150 UL S1
BYPASS SCREEN
Frequency
The frequency of the input Utility.
Voltage L1 / Voltage L2 / Voltage L3
3-phase input Utility voltage PHASE
/NEUTRAL.
Current L1 / Current L2 / Current L3
Input Utility current for the 3-phases.
Main failure count
The total number of minor Utility faults (Bypass Utility out of tolerance faults).
Number of fast transients
The number of fast transients occurred on the bypass utility on the last seven days.
Bypass quality index
The statistic evaluation in % (100= good; 0= bad) of the Bypass utility.
Status
Bypass status: free / blocked.
INVERTER SCREEN
Frequency
The output frequency of the Inverter.
Voltage L1 / Voltage L2 / Voltage L3
3-phase output
Utility
voltage
PHASE/NEUTRAL.
Status
The synchronization status of the
Inverter with respect to Utility:
-
Synchronized.
-
Not synchronized.
Temperature
“XXX” indicates disabled function.
Temperature 1 / 2 / 3
Temperature of the Inverter bridge (Power Module 1 / 2 / 3).