Critical Power
Modifications reserved
Page 27/60
GE_UPS_ISG_TLE_SUL_M16_M50_2bU_V010.docx
Installation Guide
TLE Series 160 - 500 UL S2B
Size of Branch Circuit Over Current Protection - All Models: - "CAUTION - To reduce the risk of fire,
only connect UPS to a circuit provided with (see below) maximum amperes branch circuit over
current protection in accordance with the NEC (National Electric Code), NSI / NFPA 70
UPS rating
F1 - AC Input Rectifier F2 -AC Input Bypass
F3 - AC Input
F4 - DC Input
80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated 80% Rated 100% Rated
TLE Series 160
300 A
250 A
250 A
200 A
300 A
250 A
400 A
400 A
TLE Series 200
350 A
300 A
300 A
250 A
350 A
300 A
500 A
500 A
TLE Series 225
400 A
350 A
350 A
300 A
400 A
350 A
600 A
600 A
TLE Series 250
450 A
350 A
400 A
350 A
450 A
350 A
600 A
600 A
TLE Series 300
600 A
450 A
500 A
400 A
600 A
450 A
800 A
800 A
TLE Series 400
700 A
600 A
600 A
500 A
700 A
600 A
1000 A
1000 A
TLE Series 500
900 A
700 A
800 A
700 A
900 A
700 A
1200 A
1200 A
WIRING
Wire sizing according to:
NEC Section 210-20 (A) Table 310-16.
Use 167°F (75°C) copper or aluminum wire.
Wiring requirements:
AC INPUT RECTIFIER:
3-Phase, 4 wire plus Ground
AC INPUT BYPASS:
3-Phase, 4 wire plus Ground
AC OUTPUT:
3-Phase, 4 wire plus Ground
DC INPUT:
2 wire (positive and negative) plus Ground
Maximum recommended cable size
UPS rating
Rectifier Input Bypass Input
DC Input
AC Output
GND
TLE Series 160
2 x 3/0 AWG
2 x 2/0 AWG
2 x 300 kcmil
2 x 2/0 AWG
1 x 3 AWG
TLE Series 200
2 x 4/0 AWG
2 x 3/0 AWG
2x 400 kcmil
2 x 3/0 AWG
1 x 2 AWG
TLE Series 225
2 x 300 kcmil
2 x 2/0 AWG
2 x 600 kcmil
2 x 2/0 AWG
1 x 1 AWG
TLE Series 250
2 x 350 kcmil
2 x 300 kcmil
2 x 600 kcmil
2 x 300 kcmil
1 x 1 AWG
TLE Series 300
3 x 300 kcmil
2x 400 kcmil
3 x 500 kcmil
2x 400 kcmil
1 x 1/0 AWG
TLE Series 400
4 x 4/0 AWG
4 x 3/0 AWG
4 x 400 kcmil
4 x 3/0 AWG
1 x 2/0 AWG
TLE Series 500
4 x 350 kcmil
4 x 300 kcmil
4 x 600 kcmil
4 x 300 kcmil
1 x 3/0 AWG