4.3 GE MIB OBJECTS
GE provides private MIBs, which enhance the UPS information available over SNMP interface.
These MIBs are only supported on 3-ph SNMP/Web plug-in adapter.
Two different version of the GE private MIB exist:
•
GE Single MIB: to be used for monitoring of a 3-ph UPS is single unit configuration
•
GE Parallel MIB: to be used for monitoring of a 3-ph parallel UPS system
The MIB structure is shown in the following picture. The
geGenericUPS
group provides information on
the unit in stand-alone configuration or on the overall system in a parallel configuration. The
geFirstUPS
…
geEightUPS
groups provide information on the units that are part of a parallel configuration.
geUPS
(1.3.6.1.4.1.818.1.1)
geGenericUPS(10)
geFirstUPS(11)
geSecondUPS(12)
…
geEigthUPS(18)
Parallel
system
only
geUPS
(1.3.6.1.4.1.818.1.1)
geGenericUPS(10)
geFirstUPS(11)
geSecondUPS(12)
…
geEigthUPS(18)
Parallel
system
only
For each of these groups the 3-ph SNMP/Web plug-in adapter supports the following objects.
(Objects marked with [*] do not have a RFC1628 correspondence)
OIDs
TRAPS & ALARMS
====
upsIdent
Group ====
upsIdentManufacturer
upsIdentModel
upsIdentUPSSoftwareVersion
upsIdentAgentSoftwareVersion
upsIdentName
upsIdentAttachedDevices
upsIdentsUPSSerialNumber [*]
upsIdentComProtVersion [*]
upsIdentOperatingTime [*]
====
uspBattery
Group ====
upsBatteryStatus
upsSecondsOnBattery
upsEstimatedMinutesRemaining
upsEstimatedChargeRemaining
upsBatteryVoltage
upsBatteryCurrent
upsBatteryTemperature
upsBatteryRipple [*]
====
upsInput
Group ====
upsInputLineBads
upsInputNumLines
upsInputFrequency
====
geUPSTraps
&
upsWellKnownAlarms
group
====
upsAlarmBatteryBad
upsAlarmOnBattery
upsAlarmLowBattery
upsAlarmDepletedBattery
upsAlarmTempBad
upsAlarmInputBad
upsAlarmOutputBad
upsAlarmOutputOverload
upsAlarmOnBypass
upsAlarmBypassBad
upsAlarmOutputOffAsRequested
upsAlarmUpsOffAsRequested
upsAlarmChargerFailed
upsAlarmUpsOutputOff
upsAlarmUpsSystemOff
upsAlarmFanFailure
upsAlarmFuseFailure
upsAlarmGeneralFault
upsAlarmDiagnosticTestFailed
upsAlarmCommunicationsLost
upsAlarmAwaitingPower
upsAlarmShutdownPending
upsAlarmShutdownImminent