Address
Word
1
Word 2
Type
Description
Notes
30X08 30X09 FLOAT Input Frequency L1
The present input frequency.
Units
: Hertz
30X10 30X11 FLOAT Input Voltage L1
The present input voltage, RMS value.
Units
: Volts
30X12 30X13 FLOAT Input Current L1
The present input current, RMS value.
Units
: Amp
30X14 30X15 FLOAT Input True Power L1
The present input true power.
Units
: Watts
30X16 30X17 FLOAT Input Frequency L2
The present input frequency.
Units
: Hertz
30X18 30X19 FLOAT Input Voltage L2
The present input voltage, RMS value.
Units
: Volts
30X20 30X21 FLOAT Input Current L2
The present input current, RMS value.
Units
: Amp
30X22 30X23 FLOAT Input True Power L2
The present input true power.
Units
: Watts
30X24 30X25 FLOAT Input Frequency L3
The present input frequency.
Units
: Hertz
30X26 30X27 FLOAT Input Voltage L3
The present input voltage, RMS value.
Units
: Volts
30X28 30X29 FLOAT Input Current L3
The present input current, RMS value.
Units
: Amp
30X30 30X31 FLOAT Input True Power L3
The present input true power.
Units
: Watts
30X32 30X33 FLOAT Output Frequency
The present output frequency.
Units
: Hertz
30X34 30X35 FLOAT Output Voltage L1
The present output voltage, RMS value.
Units
: Volts
30X36 30X37 FLOAT Output Current L1
The present output current, RMS value.
Units
: Amp
30X38 30X39 FLOAT Output Power L1
The present output true power.
Units
: Watts
30X40 30X41 FLOAT Output Percent Load L1
The percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of the
percent load of true power capacity and the percent
load of VA.
30X42 30X43 FLOAT Output Voltage L2
The present output voltage, RMS value.
Units
: Volts
30X44 30X45 FLOAT Output Current L2
The present output current, RMS value.
Units
: Amp
30X46 30X47 FLOAT Output Power L2
The present output true power.
Units
: Watts
30X48 30X49 FLOAT Output Percent Load L2
The percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of the
percent load of true power capacity and the percent
load of VA.
30X50 30X51 FLOAT Output Voltage L3
The present output voltage, RMS value.
Units
: Volts
30X52 30X53 FLOAT Output Current L3
The present output current, RMS value.
Units
: Amp
30X54 30X55 FLOAT Output Power L3
The present output true power.
Units
: Watts
30X56 30X57 FLOAT Output Percent Load L3
The percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of the
percent load of true power capacity and the percent
load of VA.
30X58 30X59 FLOAT Bypass Frequency
The present bypass frequency.
Units
: Hertz
30X60 30X61 FLOAT Bypass Voltage L1
The present bypass voltage, RMS value.
Units
: Volts
30X62 30X63 FLOAT Bypass Current L1
The present bypass current, RMS value.
Units
: Amp
30X64 30X65 FLOAT Bypass Power L1
The present bypass true power.
Units
: Watts
30X66 30X67 FLOAT Bypass Voltage L2
The present bypass voltage, RMS value.
Units
: Volts
30X68 30X69 FLOAT Bypass Current L2
The present bypass current, RMS value.
Units
: Amp
30X70 30X71 FLOAT Bypass Power L2
The present bypass true power.
Units
: Watts
30X72 30X73 FLOAT Bypass Voltage L3
The present bypass voltage, RMS value.
Units
: Volts
30X74 30X75 FLOAT Bypass Current L3
The present bypass current, RMS value.
Units
: Amp
30X76 30X77 FLOAT Bypass Power L3
The present bypass true power.
Units
: Watts
30X78 30X79 FLOAT Est. Minute Remaining
An estimate of the time to battery charge depletion
under the present load conditions if the utility power is
off and remains off, or if it were to be lost and remain
off.
Units
: Minutes
30X80 30X81 FLOAT Est.
Charge
Remaining
An estimate of the battery charge remaining
expressed as a percent of full charge.
30X82 30X83 FLOAT Battery Voltage
The present battery voltage.
Units
: Volts
30X84 30X85 FLOAT Battery Current
The present battery current (into battery).
Units
: Amp.
Positive values for currents going into the battery.
30X86 30X87 FLOAT Battery Temperature
The ambient temperature at or near the UPS Battery
casing.
Units
: degrees centigrade (°C)