Address Description
Notes
10X32 -
Not
Used
(Reserved)
10X33
upsStatusEcomodeIsOn
Ecomode is ON.
10X34
upsStatusBatteryIsCharging
Battery is being charged.
10X35
upsStatusBatteryIsDischarging
The UPS is drawing power from the batteries. Identical to
upsAlarmOnBattery
.
10X36
upsStatusAlarmIsActive
UPS has a general fault. Identical to
upsAlarmGeneralFault
.
10X37 upsStatusRectifierIsOn Rectified
is
ON.
10X38
upsStatusStopOperation
The remaining battery run time is less than or equal to
upsConfigLowBattTime
or any other condition exist, such
that the output will be disconnected in a short time.
10X39
upsStatusOnBypass
The Bypass is presently engaged on the UPS. Identical to
upsAlarmOnBypass
.
10X40
upsStatusMainsBypassOK
All input conditions on the Bypass are OK. Reciprocal to
upsAlarmBypassBad
.
10X41
upsStatusMainsRectifierOK
All input conditions on the rectifier are OK. Reciprocal to
upsAlarmInputBad
.
10X42
upsStatusDetourIsOn
The manual deviation is on.
10X43
upsStatusAcousticAlarmIsOn
The acoustic alarm is on, as a consequence of a new fault.
10X44 upsStatusServiceCheck
A
general maintenance or a specific UPS component check
is required.
10X45
upsStatusInverterIsOn
The Inverter is switched on.
10X46
upsStatusNotInParallel
The UPS belongs to a parallel system but does not supply
the load (disconnected).
10X47
upsStatusResetLoadOff
The load is not supplied and special action has to be
performed prior to be able to restart.
10X48
upsStatusLoadOff
The load is not supplied
10X49 upsStatusBoostMode
Boost
mode
10X50 upsStatusBuckMode
Buck
mode
10X51
upsStatusIemModeIsOn
IEM (Intelligent Energy Management) mode is active
10X52 upsStatus5thFilterIsOn
5
th
order harmonic filter is inserted
(SCR-based rectifier only)
10X53 upsStatus11thFilterIsOn
11
th
order harmonic filter is inserted
(SCR-based rectifier only)
10X54
upsStatus2ndRectifierBridgeIsOn
For units featuring two separate rectifier bridges (typically
large 3-ph UPSs), the 2
nd
rectifier bridge is on.
10X55
-
Reserved for future enhancements
10X56
-
Reserved for future enhancements
10X57
-
Reserved for future enhancements
10X58
-
Reserved for future enhancements
10X59
-
Reserved for future enhancements
10X60
-
Reserved for future enhancements
10X61
upsGlobalParallelValues
The set of registers pertains to the whole parallel system
rather than specific UPS in the system.
10X62
-
Reserved for future enhancements
10X63
-
Reserved for future enhancements
10X64
-
Reserved for future enhancements
NOTE
: Registers 10X26 – 10X31 hold different contents in 1-ph and 3-ph UPS.
Registers 10X33 – 10X64 are only available on 3-ph UPS.
NOTE
: GT Series 5-10kVA UL UPSs are 2-ph systems.
In this case, the L-L voltage is mapped to Line3 Voltage registers.
Modifications reserved
Page 51/69
OPM_CNT_SNM_BAS_CRD_1GB_V014.doc
Operating Manual
SNMP/Web Adapter