Discrete Inputs
(1xxxx) –
Function code 02: Read Discrete Input
Address Description
Notes
10X01
upsAlarmBatteryBad
One or more batteries have been determined to require
replacement.
10X02
upsAlarmOnBattery
The UPS is drawing power from the batteries.
10X03
upsAlarmLowBattery
The remaining battery run-time is less than or equal to
upsConfigLowBattTime
.
10X04
upsAlarmDepletedBattery
The UPS will be unable to sustain the present load when
and if the utility power is lost.
10X05
upsAlarmTempBad
A temperature is out of tolerance.
10X06
upsAlarmInputBad
An input condition is out of tolerance.
10X07 upsAlarmOutputBad
An
output condition (other than
OutputOverload
) is out of
tolerance.
10X08
upsAlarmOutputOverload
The output load exceeds the UPS output capacity.
10X09
upsAlarmOnBypass
The Bypass is presently engaged on the UPS.
10X10
upsAlarmBypassBad
The Bypass is out of tolerance.
10X11
upsAlarmOutputOffAsRequested
The UPS has shutdown as requested, i.e., the output is off.
10X12
upsAlarmUpsOffAsRequested
The entire UPS has shutdown as commanded.
10X13
upsAlarmChargerFailed
An uncorrected problem has been detected within the UPS
charger subsystem.
10X14
upsAlarmUpsOutputOff
The output of the UPS is in the off state.
10X15
upsAlarmUpsSystemOff
The UPS system is in the off state.
10X16
upsAlarmFanFailure
The failure of one or more UPS fans has been detected.
10X17
upsAlarmFuseFailure
The failure of one or more fuses has been detected.
10X18
upsAlarmGeneralFault
A general fault in the UPS has been detected.
10X19
upsAlarmDiagnosticTestFailed
The result of the last diagnostic test indicates a failure.
10X20
upsAlarmCommunicationsLost
A problem has been encountered in the communications
between the agent and the UPS.
10X21
upsAlarmAwaitingPower
The UPS output is off and the UPS is awaiting the return of
input power.
10X22
upsAlarmShutdownPending
A Shutdown countdown is underway.
10X23
upsAlarmShutdownImminent
The UPS will turn off power to the load in less than 5
seconds; this may be either a timed shutdown or a low
battery shutdown.
10X24
upsAlarmTestInProgress
A test is in progress.
10X25
upsAlarmReceptacleOff
One or more receptacles are switched off.
10X26 VoltageOnOutput
(1-ph only)
upsAlarmHighSpeedBusFailure
(3-ph only)
A voltage has been detected on output in a unforeseen
situation
A problem on the High Speed Bus communication is
detected
10X27 DCLinkVoltageBad
(1-ph only)
upsAlarmHighSpeedBusJACRCFailure
(3-ph only)
The DC Link Voltage reached a high level.
A CRC problem on the Highspeed Bus JA is detected.
10X28 InputCircuitFailure
(1-ph only)
upsAlarmConnectivityBusFailure
(3-ph only)
ByBf micro processor, IC converter, BF relay or charger is
defect.
A problem on the Connectivity Bus communication is
detected
10X29 ChargeConverterError
(1-ph only)
upsAlarmHighSpeedBusJBCRCFailure
(3-ph only)
Charge converter or DC Capacitors are defect.
A CRC problem on the Highspeed Bus JB is detected.
10X30 BypassDefect
(1-ph only)
UpsAlarmCurrentSharing
(3-ph only)
Bypass is not able to hold Output Voltage.
The System detects an high current sharing on the parallel
system.
10X31 PhaseNeutralReversal
(1-ph only)
UpsAlarmDCRipple
(3-ph only)
There is a voltage between ground and neutral (input
reversed).
The System detects an high ripple voltage on one DC link.