![GE D20MX Instruction Manual Download Page 99](http://html.mh-extra.com/html/ge/d20mx/d20mx_instruction-manual_122958099.webp)
D20MX INSTRUCTION MANUAL
GE INFORMATION
99
D20MX Processor
Appendix A: Default Role-Based
Access Control Model
Default Role-Based Access Control Model
Configured roles in the D20MX
When you configure the D20MX to use RADIUS, the D20MX must be configured with a set
of roles in the B014 RADIUS Roles Table (B014RADR) of the WESMAINT II+ application (Refer
to the
B014-1NCG WESMAINT II+ for the D20MX Configuration Guide
for more information).
The role is identified by a role ID, which is an integer number provided by the RADIUS
server.
The D20MX Default configurations D20MX01-14X and D20MX02-14X include a default
role-based access control model that meets the general rules shown in Table 21.
Table 21: General access control rules
The Shell access level roles are provided in Table 22
Table 22: Shell access level
Description
Administrator
(2)
Engineer
(1)
Operator
(3)
Observer
(0)
Can Change Passwords
Yes
No
No
No
Can Clear the Login Buffer
No
No
No
No
Can Change SCADA Settings
Yes
Yes
No
No
Can Download Firmware
Yes
Yes
No
No
Can Perform Operational Control (e.g. breaker
operation)
Yes
Yes
Yes
No
Can View Operational Data
Yes
Yes
Yes
Yes
Can Access Low Level “C” Shell
Yes
No
No
No
Description
Administrator
(2)
Engineer
(1)
Operator
(3)
Observer
(0)
Access Level
Read/Write
Maintenance Read Only Read Only
Summary of Contents for D20MX
Page 10: ...10 GE INFORMATION D20MX INSTRUCTION MANUAL ABOUT THIS DOCUMENT ...
Page 32: ...32 GE INFORMATION D20MX INSTRUCTION MANUAL CHAPTER 1 BEFORE YOU START ...
Page 90: ...90 GE INFORMATION D20MX INSTRUCTION MANUAL CHAPTER 5 CONFIGURING THE SOFTWARE ...
Page 112: ...112 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX B STANDARDS PROTECTION ...
Page 116: ...116 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX C FREQUENTLY ASKED QUESTIONS ...
Page 148: ...148 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX D USING CONFIGPRO WITH D20MX ...
Page 158: ...158 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX E SECURE CONNECTION FOR LOGICLINX ...
Page 162: ...162 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX F LIST OF ACRONYMS ...
Page 168: ...168 GE INFORMATION D20MX INSTRUCTION MANUAL INDEX ...