APPENDIX E: SECURE CONNECTION FOR LOGICLINX
D20MX INSTRUCTION MANUAL
GE INFORMATION
151
3.
View the access flags for a new local user:
3.1.
Open the User Configuration table.
3.2.
Add a new row and scroll left until you see the Application Control column.
3.3.
Double-click the
Application Control
field.
Result: A dialog showing the access flags for the new user appears.
4.
Select the first row and press
Ctrl-V
to paste the application control flags from the
Engineer role to the new local user.
Result: A dialog showing the Paste Options appears.
5.
Click
OK
.
Result: The access flags for the Engineer role now appear in the new user's access flag
list.
6.
Click
OK
.
Result: The User Configuration table reappears.
7.
For the Monitor Access Level field, select
Maintenance
.
8.
For
the User Name field, type the name of the user, for example:
tom
.
9.
Click
OK
and
OK
.
Result: The Wesmaint User Configuration is closed.
LogicLinx (B082-0N) configuration
To configure B082-0N LogicLinx to require a secure connection:
1.
In the Logic Linx (B082-0N V400) Communication Types configuration table set:
a) Communications Type: Ethernet
b) SSH Tunnel: Tunnel Enabled
c) Port Number: 1100
Summary of Contents for D20MX
Page 10: ...10 GE INFORMATION D20MX INSTRUCTION MANUAL ABOUT THIS DOCUMENT ...
Page 32: ...32 GE INFORMATION D20MX INSTRUCTION MANUAL CHAPTER 1 BEFORE YOU START ...
Page 90: ...90 GE INFORMATION D20MX INSTRUCTION MANUAL CHAPTER 5 CONFIGURING THE SOFTWARE ...
Page 112: ...112 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX B STANDARDS PROTECTION ...
Page 116: ...116 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX C FREQUENTLY ASKED QUESTIONS ...
Page 148: ...148 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX D USING CONFIGPRO WITH D20MX ...
Page 158: ...158 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX E SECURE CONNECTION FOR LOGICLINX ...
Page 162: ...162 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX F LIST OF ACRONYMS ...
Page 168: ...168 GE INFORMATION D20MX INSTRUCTION MANUAL INDEX ...