11-126
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
CHAPTER 11: MODBUS MEMORY MAP
67190
0x6A35
Minimum Voltage
0
1250
1
x VT
F13
700
1
67192
0x6A37
Minimum Current
0
30000
1
x CT
F13
200
1
67194
0x6A39
Relays
0
0xFFFFFFFF
1
FC198
0
1
67196
0x6A3B
Block
0
0xFFFFFFFF
1
FC142
0
1
67198
0x6A3D
Events
0
1
1
FC126
1
1
67199
0x6A3E
Targets
0
2
1
FC101
1
1
Underfrequency 6
67210
0x6A49
Name
0
65535
1
F60_26 Underfreq 6 26
67223
0x6A56
Function
0
4
1
FC100
0
1
67224
0x6A57
Signal Input
0x12
0x22
1
FC103A 0x12
1
67225
0x6A58
Pickup
2000
6500
1
Hz
F2
5900
1
67226
0x6A59
Pickup Delay
0
6000000
1
s
F13
2000
1
67228
0x6A5B
Dropout Delay
0
6000000
1
s
F13
2000
1
67230
0x6A5D
Minimum Voltage
0
1250
1
x VT
F13
700
1
67232
0x6A5F
Minimum Current
0
30000
1
x CT
F13
200
1
67234
0x6A61
Relays
0
0xFFFFFFFF
1
FC198
0
1
67236
0x6A63
Block
0
0xFFFFFFFF
1
FC142
0
1
67238
0x6A65
Events
0
1
1
FC126
1
1
67239
0x6A66
Targets
0
2
1
FC101
1
1
Overfrequency 1
67260
0x6A7B
Name
0
65535
1
F60_26 Overfreq 1
26
67273
0x6A88
Function
0
4
1
FC100
0
1
67274
0x6A89
Signal Input
0x12
0x22
1
FC103A 0x12
1
67275
0x6A8A
Pickup
2000
6500
1
Hz
F2
6050
1
67276
0x6A8B
Pickup Delay
0
6000000
1
s
F13
5000
1
67278
0x6A8D
Dropout Delay
0
6000000
1
s
F13
5000
1
67280
0x6A8F
Minimum Voltage
0
1250
1
x VT
F13
300
1
67282
0x6A91
Relays
0
0xFFFFFFFF
1
FC198
0
1
67284
0x6A93
Block
0
0xFFFFFFFF
1
FC142
0
1
67286
0x6A95
Events
0
1
1
FC126
1
1
67287
0x6A96
Targets
0
2
1
FC101
1
1
Overfrequency 2
67298
0x6AA1
Name
0
65535
1
F60_26 Overfreq 2
26
67311
0x6AAE
Function
0
4
1
FC100
0
1
67312
0x6AAF
Signal Input
0x12
0x22
1
FC103A 0x12
1
67313
0x6AB0
Pickup
2000
6500
1
Hz
F2
6050
1
67314
0x6AB1
Pickup Delay
0
6000000
1
s
F13
5000
1
67316
0x6AB3
Dropout Delay
0
6000000
1
s
F13
5000
1
67318
0x6AB5
Minimum Voltage
0
1250
1
x VT
F13
300
1
67320
0x6AB7
Relays
0
0xFFFFFFFF
1
FC198
0
1
67322
0x6AB9
Block
0
0xFFFFFFFF
1
FC142
0
1
67324
0x6ABB
Events
0
1
1
FC126
1
1
67325
0x6ABC
Targets
0
2
1
FC101
1
1
Overfrequency 3
67336
0x6AC7
Name
0
65535
1
F60_26 Overfreq 3
26
67349
0x6AD4
Function
0
4
1
FC100
0
1
Modbus
Address
Hex
Address
Description
Min
Max
Step Units
Format
Code
Factory
Default
Size in
Words
Summary of Contents for 869