11-320
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
FORMAT CODES
CHAPTER 11: MODBUS MEMORY MAP
1
Any Two
2
All Three
FC262
unsigned 16 bits
Breaker Failure Function
0
Disabled
1
Retrip
2
Latched Alarm
3
Alarm
4
Configurable
FC263
unsigned 16 bits
Breaker Failure Supervision
0
Current
1
52b & Current
2
52b
FC264
unsigned 16 bits
Breaker Status
0
State Unknown
1
Opened
2
Closed
3
Disconnected
4
Not Configured
FC265
unsigned 16 bits
TOC Reset
0
Instantaneous
1
Timed
FC266
unsigned 32 bits
Contact Input Selection
0x0000
Off
0x200
Contact Input 1
0x201
Contact Input 2
0x202
Contact Input 3
0x203
Contact Input 4
0x204
Contact Input 5
0x205
Contact Input 6
0x206
Contact Input 7
0x207
Contact Input 8
0x208
Contact Input 9
0x209
Contact Input 10
0x20A
Contact Input 11
0x20B
Contact Input 12
0x20C
Contact Input 13
0x20D
Contact Input 14
FC267
unsigned 16 bits
Supervision Function
0
Disabled
1
Lockout
2
Alarm
FC268
unsigned 16 bits
Distance Measurement Unit
0
Miles
1
Km
FC269
unsigned 16 bits
VT Substitution
0
None
1
I0
Code
Type
Definition