8-10
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
THE IEC 61850 CONFIGURATOR
CHAPTER 8: IEC 61850
The equations to calculate minimum (min) and maximum (max) values in the MMXU
nodes are as follows:
Table 8-3: Calculate Min/Max MMXU Node Values
See the following list of supported parameters. Note that the same list is also
supported for the MSQI logical node. MSQI parameters are displayed only if the relay
supports sensitive ground CT.
MMXU Node Value
To Calculate
TotW
max = (Phase CT Primary * 46) * (Phase VT Ratio * 240) / 1000
min = -max
Note that the max is divided by 1000 to convert from W to kW
TotVar
max = (Phase CT Primary * 46) * (Phase VT Ratio * 240) / 1000
min = -max
TotVA
max = (Phase CT Primary * 46) * (Phase VT Ratio * 240) / 1000
min = -max
TotPF
max = 1
min = -1
Hz
max = 90
min = 0
HzRte
max = 15
min = -15
PPV
max = Phase VT Ratio * 240
min = 0
PhV
max = Phase VT Ratio * 240
min = 0
A$phsA, phsB, phsC
max = (Phase CT Primary * 46)
min = 0
A$neut
max = (Ground CT Primary * 46)
min = 0
A$net
max = (Phase CT Primary * 46)
min = 0
A$res
max = (Sens. Ground CT Primary * 3)
min = 0
AuxV
max = Aux. VT Ratio * 240
min = 0
SeqA$c1, c2 ,c3
max = (Phase CT Primary * 46)
min = 0
SeqV$c1, c2, c3
max = (Phase VT Ratio * 240)
min = 0
dbAng
angle dB = (DB percentage* 360)
Supported Parameters
869.MMXU1$CF$TotW$db
869.MMXU1$CF$TotVAr$db
869.MMXU1$CF$TotVA$db
869.MMXU1$CF$TotPF$db
869.MMXU1$CF$Hz$db
869.MMXU1$CF$Hz3VT$db
869.MMXU1$CF$HzVx$db
869.MMXU1$CF$PPV$phsAB$db
869.MMXU1$CF$PPV$phsAB$dbAng
869.MMXU1$CF$PPV$phsBC$db
869.MMXU1$CF$PPV$phsBC$dbAng
869.MMXU1$CF$PPV$phsCA$db