11-56
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
CHAPTER 11: MODBUS MEMORY MAP
50236
0x27FB
Voting
0
12
1
FC122
0
1
50237
0x27FC
Trip Temperature
1
250
1
°C
F20C
155
1
50238
0x27FD
Trip Pickup Delay
0
600
1
s
F0
2
1
50239
0x27FE
Trip Dropout Delay
0
600
1
s
F0
0
1
50240
0x27FF
Trip Relays
0
0xFFFFFFFF
1
FC198D 0
1
50242
0x2801
Alarm Function
0
3
1
FC100E 0
1
50243
0x2802
Alarm Temperature
1
250
1
°C
F20C
130
1
50244
0x2803
Alarm Pickup Delay
0
600
1
s
F0
2
1
50245
0x2804
Alarm Dropout Delay
0
600
1
s
F0
0
1
50246
0x2805
Alarm Relays
0
0xFFFFFFFF
1
FC198C 0
1
50248
0x2807
Sensor Open
0
2
1
FC354
0
1
50249
0x2808
Block
0
0xFFFFFFFF
1
FC142
0
1
50251
0x280A
Events
0
1
1
FC126
1
1
50252
0x280B
Targets
0
2
1
FC101
2
1
RTD 2 Input Setpoints
50253
0x280C
Trip Function
0
4
1
FC100D 0
1
50254
0x280D
Name
0
65535
1
F60_26 RTD 2
26
50267
0x281A
Type
0
3
1
FC120
0
1
50268
0x281B
Application
0
4
1
FC121
0
1
50269
0x281C
Voting
0
12
1
FC122
0
1
50270
0x281D
Trip Temperature
1
250
1
°C
F20C
155
1
50271
0x281E
Trip Pickup Delay
0
600
1
s
F0
2
1
50272
0x281F
Trip Dropout Delay
0
600
1
s
F0
0
1
50273
0x2820
Trip Relays
0
0xFFFFFFFF
1
FC198D 0
1
50275
0x2822
Alarm Function
0
3
1
FC100E 0
1
50276
0x2823
Alarm Temperature
1
250
1
°C
F20C
130
1
50277
0x2824
Alarm Pickup Delay
0
600
1
s
F0
2
1
50278
0x2825
Alarm Dropout Delay
0
600
1
s
F0
0
1
50279
0x2826
Alarm Relays
0
0xFFFFFFFF
1
FC198C 0
1
50281
0x2828
Sensor Open
0
2
1
FC354
0
1
50282
0x2829
Block
0
0xFFFFFFFF
1
FC142
0
1
50284
0x282B
Events
0
1
1
FC126
1
1
50285
0x282C
Targets
0
2
1
FC101
2
1
RTD 3 Input Setpoints
50286
0x282D
Trip Function
0
4
1
FC100D 0
1
50287
0x282E
Name
0
65535
1
F60_26 RTD 3
26
50300
0x283B
Type
0
3
1
FC120
0
1
50301
0x283C
Application
0
4
1
FC121
0
1
50302
0x283D
Voting
0
12
1
FC122
0
1
50303
0x283E
Trip Temperature
1
250
1
°C
F20C
155
1
50304
0x283F
Trip Pickup Delay
0
600
1
s
F0
2
1
50305
0x2840
Trip Dropout Delay
0
600
1
s
F0
0
1
50306
0x2841
Trip Relays
0
0xFFFFFFFF
1
FC198D 0
1
50308
0x2843
Alarm Function
0
3
1
FC100E 0
1
50309
0x2844
Alarm Temperature
1
250
1
°C
F20C
130
1
50310
0x2845
Alarm Pickup Delay
0
600
1
s
F0
2
1
Modbus
Address
Hex
Address
Description
Min
Max
Step Units
Format
Code
Factory
Default
Size in
Words