CHAPTER 11: MODBUS MEMORY MAP
MODBUS MEMORY MAP
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
11-57
50311
0x2846
Alarm Dropout Delay
0
600
1
s
F0
0
1
50312
0x2847
Alarm Relays
0
0xFFFFFFFF
1
FC198C 0
1
50314
0x2849
Sensor Open
0
2
1
FC354
0
1
50315
0x284A
Block
0
0xFFFFFFFF
1
FC142
0
1
50317
0x284C
Events
0
1
1
FC126
1
1
50318
0x284D
Targets
0
2
1
FC101
2
1
RTD 4 Input Setpoints
50319
0x284E
Trip Function
0
4
1
FC100D 0
1
50320
0x284F
Name
0
65535
1
F60_26 RTD 4
26
50333
0x285C
Type
0
3
1
FC120
0
1
50334
0x285D
Application
0
4
1
FC121
0
1
50335
0x285E
Voting
0
12
1
FC122
0
1
50336
0x285F
Trip Temperature
1
250
1
°C
F20C
155
1
50337
0x2860
Trip Pickup Delay
0
600
1
s
F0
2
1
50338
0x2861
Trip Dropout Delay
0
600
1
s
F0
0
1
50339
0x2862
Trip Relays
0
0xFFFFFFFF
1
FC198D 0
1
50341
0x2864
Alarm Function
0
3
1
FC100E 0
1
50342
0x2865
Alarm Temperature
1
250
1
°C
F20C
130
1
50343
0x2866
Alarm Pickup Delay
0
600
1
s
F0
2
1
50344
0x2867
Alarm Dropout Delay
0
600
1
s
F0
0
1
50345
0x2868
Alarm Relays
0
0xFFFFFFFF
1
FC198C 0
1
50347
0x286A
Sensor Open
0
2
1
FC354
0
1
50348
0x286B
Block
0
0xFFFFFFFF
1
FC142
0
1
50350
0x286D
Events
0
1
1
FC126
1
1
50351
0x286E
Targets
0
2
1
FC101
2
1
RTD 5 Input Setpoints
50352
0x286F
Trip Function
0
4
1
FC100D 0
1
50353
0x2870
Name
0
65535
1
F60_26 RTD 5
26
50366
0x287D
Type
0
3
1
FC120
0
1
50367
0x287E
Application
0
4
1
FC121
0
1
50368
0x287F
Voting
0
12
1
FC122
0
1
50369
0x2880
Trip Temperature
1
250
1
°C
F20C
155
1
50370
0x2881
Trip Pickup Delay
0
600
1
s
F0
2
1
50371
0x2882
Trip Dropout Delay
0
600
1
s
F0
0
1
50372
0x2883
Trip Relays
0
0xFFFFFFFF
1
FC198D 0
1
50374
0x2885
Alarm Function
0
3
1
FC100E 0
1
50375
0x2886
Alarm Temperature
1
250
1
°C
F20C
130
1
50376
0x2887
Alarm Pickup Delay
0
600
1
s
F0
2
1
50377
0x2888
Alarm Dropout Delay
0
600
1
s
F0
0
1
50378
0x2889
Alarm Relays
0
0xFFFFFFFF
1
FC198C 0
1
50380
0x288B
Sensor Open
0
2
1
FC354
0
1
50381
0x288C
Block
0
0xFFFFFFFF
1
FC142
0
1
50383
0x288E
Events
0
1
1
FC126
1
1
50384
0x288F
Targets
0
2
1
FC101
2
1
RTD 6 Input Setpoints
50385
0x2890
Trip Function
0
4
1
FC100D 0
1
Modbus
Address
Hex
Address
Description
Min
Max
Step Units
Format
Code
Factory
Default
Size in
Words
Summary of Contents for 869
Page 6: ...1 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE COMMUNICATIONS CHAPTER 1 INTRODUCTION...
Page 36: ...4 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP 3...
Page 84: ...9 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 9 FILE TRANSFER PROTOCOLS...