GE Multilin
C60 Breaker Protection System
B-33
APPENDIX B
B.4 MEMORY MAPPING
B
7F63
Auxiliary Undervoltage 1 Delay
0 to 600
s
0.01
F001
100
7F64
Auxiliary Undervoltage 1 Curve
0 to 1
---
1
F111
0 (Definite Time)
7F65
Auxiliary Undervoltage 1 Minimum Voltage
0 to 3
pu
0.001
F001
100
7F66
Auxiliary Undervoltage 1 Block
0 to 65535
---
1
F300
0
7F67
Auxiliary Undervoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7F68
Auxiliary Undervoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7F69
Reserved (7 items)
0 to 65535
---
1
F001
0
7F70
...Repeated for Auxiliary Undervoltage 2
7F80
...Repeated for Auxiliary Undervoltage 3
Frequency (Read Only)
8000
Tracking Frequency
---
Hz
---
F001
0
EGD Fast Production Status (Read Only)
83E0
EGD Fast Producer Exchange 1 Signature
0 to 65535
---
1
F001
0
83E1
EGD Fast Producer Exchange 1 Configuration Time
0 to 4294967295
---
---
F003
0
83E3
EGD Fast Producer Exchange 1 Size
0 to 65535
---
1
F001
0
EGD Slow Production Status (Read Only) (2 modules)
83F0
EGD Slow Producer Exchange 1 Signature
0 to 65535
---
1
F001
0
83F1
EGD Slow Producer Exchange 1 Configuration Time
0 to 4294967295
---
---
F003
0
83F3
EGD Slow Producer Exchange 1 Size
0 to 65535
---
1
F001
0
83F4
...Repeated for module number 2
EGD Fast Production (Read/Write Setting)
8400
EGD Fast Producer Exchange 1 Function
0 to 1
---
1
F102
0 (Disabled)
8401
EGD Fast Producer Exchange 1 Destination
0 to 4294967295
---
1
F003
0
8403
EGD Fast Producer Exchange 1 Data Rate
50 to 1000
ms
50
F001
1000
8404
EGD Fast Producer Exchange 1 Data Item 1 (20 items)
0 to 65535
---
1
F001
0
8418
Reserved (80 items)
---
---
---
F001
0
EGD Slow Production (Read/Write Setting) (2 modules)
8500
EGD Slow Producer Exchange 1 Function
0 to 1
---
1
F102
0 (Disabled)
8501
EGD Fast Producer Exchange 1 Destination
0 to 4294967295
---
1
F003
0
8503
EGD Slow Producer Exchange 1 Data Rate
500 to 1000
ms
50
F001
1000
8504
EGD Slow Producer Exchange 1 Data Item 1 (50 items)
0 to 65535
---
1
F001
0
8536
Reserved (50 items)
---
---
---
F001
0
8568
...Repeated for EGD Exchange 2
Breaker Failure (Read/Write Grouped Setting) (2 modules)
8600
Breaker Failure 1 Function
0 to 1
---
1
F102
0 (Disabled)
8601
Breaker Failure 1 Mode
0 to 1
---
1
F157
0 (3-Pole)
8602
Breaker Failure 1 Source
0 to 5
---
1
F167
0 (SRC 1)
8603
Breaker Failure 1 Amp Supervision
0 to 1
---
1
F126
1 (Yes)
8604
Breaker Failure 1 Use Seal-In
0 to 1
---
1
F126
1 (Yes)
8605
Breaker Failure 1 Three Pole Initiate
0 to 65535
---
1
F300
0
8606
Breaker Failure 1 Block
0 to 65535
---
1
F300
0
8607
Breaker Failure 1 Phase Amp Supv Pickup
0.001 to 30
pu
0.001
F001
1050
8608
Breaker Failure 1 Neutral Amp Supv Pickup
0.001 to 30
pu
0.001
F001
1050
8609
Breaker Failure 1 Use Timer 1
0 to 1
---
1
F126
1 (Yes)
860A
Breaker Failure 1 Timer 1 Pickup
0 to 65.535
s
0.001
F001
0
860B
Breaker Failure 1 Use Timer 2
0 to 1
---
1
F126
1 (Yes)
860C
Breaker Failure 1 Timer 2 Pickup
0 to 65.535
s
0.001
F001
0
860D
Breaker Failure 1 Use Timer 3
0 to 1
---
1
F126
1 (Yes)
860E
Breaker Failure 1 Timer 3 Pickup
0 to 65.535
s
0.001
F001
0
860F
Breaker Failure 1 Breaker Status 1 Phase A/3P
0 to 65535
---
1
F300
0
8610
Breaker Failure 1 Breaker Status 2 Phase A/3P
0 to 65535
---
1
F300
0
8611
Breaker Failure 1 Breaker Test On
0 to 65535
---
1
F300
0
8612
Breaker Failure 1 Phase Amp Hiset Pickup
0.001 to 30
pu
0.001
F001
1050
8613
Breaker Failure 1 Neutral Amp Hiset Pickup
0.001 to 30
pu
0.001
F001
1050
Table B–9: MODBUS MEMORY MAP (Sheet 26 of 50)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for C60
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX ...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...