GE Multilin
C60 Breaker Protection System
5-33
5 SETTINGS
5.2 PRODUCT SETUP
5
h) WEB SERVER HTTP PROTOCOL
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
WEB SERVER HTTP PROTOCOL
The C60 contains an embedded web server and is capable of transferring web pages to a web browser such as Microsoft
Internet Explorer or Mozilla Firefox. This feature is available only if the C60 has the ethernet option installed. The web
pages are organized as a series of menus that can be accessed starting at the C60 “Main Menu”. Web pages are available
showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, etc. The web pages can be
accessed by connecting the UR and a computer to an ethernet network. The main menu will be displayed in the web
browser on the computer simply by entering the IP address of the C60 into the “Address” box on the web browser.
i) TFTP PROTOCOL
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
TFTP PROTOCOL
The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the C60 over a network. The C60 operates as a
TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The
dir.txt
file
obtained from the C60 contains a list and description of all available files (event records, oscillography, etc.).
j) IEC 60870-5-104 PROTOCOL
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
IEC 60870-5-104 PROTOCOL
WEB SERVER
HTTP PROTOCOL
HTTP TCP PORT
NUMBER: 80
Range: 1 to 65535 in steps of 1
TFTP PROTOCOL
TFTP MAIN UDP PORT
NUMBER: 69
Range: 1 to 65535 in steps of 1
MESSAGE
TFTP DATA UDP PORT 1
NUMBER: 0
Range: 0 to 65535 in steps of 1
MESSAGE
TFTP DATA UDP PORT 2
NUMBER: 0
Range: 0 to 65535 in steps of 1
IEC 60870-5-104
PROTOCOL
IEC 60870-5-104
FUNCTION: Disabled
Range: Enabled, Disabled
MESSAGE
IEC TCP PORT
NUMBER: 2404
Range: 1 to 65535 in steps of 1
MESSAGE
IEC NETWORK
CLIENT ADDRESSES
MESSAGE
IEC COMMON ADDRESS
OF ASDU:
0
Range: 0 to 65535 in steps of 1
MESSAGE
IEC CYCLIC DATA
PERIOD:
60 s
Range: 1 to 65535 s in steps of 1
MESSAGE
IEC CURRENT DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC VOLTAGE DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC POWER DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC ENERGY DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC OTHER DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
Summary of Contents for C60
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX ...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...