B-14
C60 Breaker Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
Breaker Arcing Current Actuals (Read Only Non-Volatile) (2 modules)
21E0
Breaker 1 Arcing Current Phase A
0 to 99999999
kA
2
-cyc
1
F060
0
21E2
Breaker 1 Arcing Current Phase B
0 to 99999999
kA
2
-cyc
1
F060
0
21E4
Breaker 1 Arcing Current Phase C
0 to 99999999
kA
2
-cyc
1
F060
0
21E6
Breaker 1 Operating Time Phase A
0 to 65535
ms
1
F001
0
21E7
Breaker 1 Operating Time Phase B
0 to 65535
ms
1
F001
0
21E8
Breaker 1 Operating Time Phase C
0 to 65535
ms
1
F001
0
21E9
Breaker 1 Operating Time
0 to 65535
ms
1
F001
0
21EA
...Repeated for Breaker Arcing Current 2
Breaker Arcing Current Commands (Read/Write Command) (2 modules)
2224
Breaker 1 Arcing Current Clear Command
0 to 1
---
1
F126
0 (No)
2225
Breaker 2 Arcing Current Clear Command
0 to 1
---
1
F126
0 (No)
Passwords Unauthorized Access (Read/Write Command)
2230
Reset Unauthorized Access
0 to 1
---
1
F126
0 (No)
Fault Location (Read Only) (5 modules)
2340
Fault 1 Prefault Phase A Current Magnitude
0 to 999999.999
A
0.001
F060
0
2342
Fault 1 Prefault Phase A Current Angle
-359.9 to 0
degrees
0.1
F002
0
2343
Fault 1 Prefault Phase B Current Magnitude
0 to 999999.999
A
0.001
F060
0
2345
Fault 1 Prefault Phase B Current Angle
-359.9 to 0
degrees
0.1
F002
0
2346
Fault 1 Prefault Phase C Current Magnitude
0 to 999999.999
A
0.001
F060
0
2348
Fault 1 Prefault Phase C Current Angle
-359.9 to 0
degrees
0.1
F002
0
2349
Fault 1 Prefault Phase A Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
234B
Fault 1 Prefault Phase A Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
234C
Fault 1 Prefault Phase B Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
234E
Fault 1 Prefault Phase B Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
234F
Fault 1 Prefault Phase C Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
2351
Fault 1 Prefault Phase C Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
2352
Fault 1 Phase A Current Magnitude
0 to 999999.999
A
0.001
F060
0
2354
Fault 1 Phase A Current Angle
-359.9 to 0
degrees
0.1
F002
0
2355
Fault 1 Phase B Current Magnitude
0 to 999999.999
A
0.001
F060
0
2357
Fault 1 Phase B Current Angle
-359.9 to 0
degrees
0.1
F002
0
2358
Fault 1 Phase C Current Magnitude
0 to 999999.999
A
0.001
F060
0
235A
Fault 1 Phase C Current Angle
-359.9 to 0
degrees
0.1
F002
0
235B
Fault 1 Phase A Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
235D
Fault 1 Phase A Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
235E
Fault 1 Phase B Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
2360
Fault 1 Phase B Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
2361
Fault 1 Phase C Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
2363
Fault 1 Phase C Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
2364
Fault 1 Type
0 to 11
---
1
F148
0 (NA)
2365
Fault 1 Location based on Line length units (km or miles)
-3276.7 to 3276.7
---
0.1
F002
0
2366
...Repeated for Fault 2
238C
...Repeated for Fault 3
23B2
...Repeated for Fault 4
23D8
...Repeated for Fault 5
Synchrocheck Actuals (Read Only) (2 modules)
2400
Synchrocheck 1 Delta Voltage
-1000000000000 to
1000000000000
V
1
F060
0
2402
Synchrocheck 1 Delta Frequency
0 to 655.35
Hz
0.01
F001
0
2403
Synchrocheck 1 Delta Phase
0 to 179.9
degrees
0.1
F001
0
2404
...Repeated for Synchrocheck 2
Autoreclose Status (Read Only) (6 modules)
2410
Autoreclose 1 Count
0 to 65535
---
1
F001
0
2411
Autoreclose 2 Count
0 to 65535
---
1
F001
0
Table B–9: MODBUS MEMORY MAP (Sheet 7 of 50)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for C60
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX ...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...