5-20
C60 Breaker Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
The
DNP MESSAGE FRAGMENT SIZE
setting determines the size, in bytes, at which message fragmentation occurs. Large
fragment sizes allow for more efficient throughput; smaller fragment sizes cause more application layer confirmations to be
necessary which can provide for more robust data transfer over noisy communication channels.
When the DNP data points (analog inputs and/or binary inputs) are configured for Ethernet-enabled relays,
check the “DNP Points Lists” C60 web page to view the points lists. This page can be viewed with a web
browser by entering the C60 IP address to access the C60 “Main Menu”, then by selecting the “Device
Information Menu” > “DNP Points Lists” menu item.
The
DNP OBJECT 1 DEFAULT VARIATION
to
DNP OBJECT 32 DEFAULT VARIATION
settings allow the user to select the DNP
default variation number for object types 1, 2, 20, 21, 22, 23, 30, and 32. The default variation refers to the variation
response when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. Refer to the
DNP implementation
section in
appendix E for additional details.
The DNP binary outputs typically map one-to-one to IED data points. That is, each DNP binary output controls a single
physical or virtual control point in an IED. In the C60 relay, DNP binary outputs are mapped to virtual inputs. However, some
legacy DNP implementations use a mapping of one DNP binary output to two physical or virtual control points to support
the concept of trip/close (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP
master can operate a single point for both trip and close, or raise and lower, operations. The C60 can be configured to sup-
port paired control points, with each paired control point operating two virtual inputs. The
DNP NUMBER OF PAIRED CONTROL
POINTS
setting allows configuration of from 0 to 32 binary output paired controls. Points not configured as paired operate on
a one-to-one basis.
The
DNP ADDRESS
setting is the DNP slave address. This number identifies the C60 on a DNP communications link. Each
DNP slave should be assigned a unique address.
The
DNP TCP CONNECTION TIMEOUT
setting specifies a time delay for the detection of dead network TCP connections. If
there is no data traffic on a DNP TCP connection for greater than the time specified by this setting, the connection will be
aborted by the C60. This frees up the connection to be re-used by a client.
Relay power must be re-cycled after changing the
DNP TCP CONNECTION TIMEOUT
setting for the changes to take
effect.
f) DNP / IEC 60870-5-104 POINT LISTS
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
DNP / IEC104 POINT LISTS
The binary and analog inputs points for the DNP protocol, or the MSP and MME points for IEC 60870-5-104 protocol, can
configured to a maximum of 256 points. The value for each point is user-programmable and can be configured by assigning
FlexLogic™ operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points.
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) is shown below.
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
DNP / IEC104 POINT LISTS
Ö
BINARY INPUT / MSP POINTS
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic™ operand. Refer to the
Introduction to FlexLogic™
section in this chapter for the full
range of assignable operands.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) is shown below.
DNP / IEC104
POINT LISTS
BINARY INPUT / MSP
POINTS
Range: see sub-menu below
MESSAGE
ANALOG INPUT / MME
POINTS
Range: see sub-menu below
BINARY INPUT / MSP
POINTS
Point:
0
Off
Range: FlexLogic™ operand
MESSAGE
Point:
1
Off
Range: FlexLogic™ operand
↓
MESSAGE
Point:
255
Off
Range: FlexLogic™ operand
NOTE
NOTE
Summary of Contents for C60
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX ...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...