General Installation
Wire Size
Page 16
MDE-4319A TopKAT Fuel Managment System Installation Manual · November 2005
115 Volt Wire Gauge Sizes per Feet/Meters of Run (Note)
Motor
H.P.
25’
7.6M
50’
15.2M
100’
30.5M
150’
45.7M
200’
61M
250’
76.2M
300’
91.4M
1/2
14
12
10
8
8
8
8
3/4
14
12
10
8
8
6
4
Note: For run over 300 feet, use relay at motor location.
230 Volt Wire Gauge Sizes per Feet/Meters of Run (Note)
Motor
H.P.
25’
7.6M
50’
15.2M
100’
30.5M
150’
45.7M
200’
61M
250’
76.2M
300’
91.4M
1/2
14
12
12
12
10
10
10
3/4
14
12
12
10
10
10
8
1-1/2
12
12
10
10
8
8
8
Note: For run over 300 feet, use relay at motor location.