GASBOY Series 9820Q
24
MDE-4339 9820Q ASTRA Installation/Operation • July 2004
023867 Wiring Diagram,
Models: 9822Q-2, 9823Q-2
International 230VAC
NOTES:
1.
All wiring and conduit runs must conform with all building/fire codes, all Federal, State, and
Local codes, National Electrical Code, (NFPA 70), NFPA 30, and Automotive and Marine
Service Station Code (NFPA 30A) codes and regulations. Canadian users must also comply
with the Canadian Electrical Code.
2.
If the
PUMP MOTOR
line is controlled by a fuel management system using solid state
relays, a resistor assembly must be installed between the Pump Motor Feed line and Neutral to
prevent false triggering of the authorization input. The resistor assembly is 30K OHM, 10
Watt (P/N C06683) for 230 VAC international wiring.
3.
SLOW FLOW
and
FAST FLOW
lines are typically used when connecting to an optional
valve. Each of these lines is capable of supplying 300 mA AC maximum (170 mA AC
maximum if already connected to the optional valve).
These lines must not be shorted to
any conduit or chassis metal, mis-wired, or connected to any equipment requiring more
than stated maximum allowable current. If these restrictions are not followed, damage
to the CPU PCB will occur.
4.
Use the wire size chart listed when determining the wire size for the control wiring.
Summary of Contents for 9822Q
Page 1: ...Series 9820Q ASTRA Installation Operation Manual MDE 4339 formerly 035090...
Page 18: ...GASBOY Series 9820Q 12 MDE 4339 9820Q ASTRA Installation Operation July 2004...
Page 22: ...GASBOY Series 9820Q 16 MDE 4339 9820Q ASTRA Installation Operation July 2004...
Page 32: ...GASBOY Series 9820Q 26 MDE 4339 9820Q ASTRA Installation Operation July 2004...