GASBOY Series 9820Q
22
MDE-4339 9820Q ASTRA Installation/Operation • July 2004
023866 Wiring Diagram, Models: 9822Q, 9823Q
Domestic 115/230 VAC
NOTES:
1.
All wiring and conduit runs must conform with all building/fire codes, all Federal, State, and
Local codes, National Electrical Code, (NFPA 70), NFPA 30, and Automotive and Marine
Service Station Code (NFPA 30A) codes and regulations. Canadian users must also comply
with the Canadian Electrical Code.
2.
Pump motor can be wired as 230 VAC to reduce current draw. See breakaway view of
230
VAC PUMP MOTOR
. All other wiring should remain the same except for the addition of
the L2 (requires 230 VAC breaker for control). If connected to equipment requiring control
of the authorization input, the Phase 2 Feed should be switched through a separate relay to
prevent false triggering of the authorization signal.
3.
If the
PUMP MOTOR
line is controlled by a fuel management system using solid state
relays, a resistor assembly must be installed between the Pump Motor Feed line and Neutral to
prevent false triggering of the authorization input. The resistor assembly is 8.2K OHM, 10
Watt (P/N C05818) for 115/230 VAC domestic and 30K OHM, 10 Watt (P/N C06683) for
230 VAC international wiring.
4.
SLOW FLOW
and
FAST FLOW
lines are typically used when connecting to an optional
valve. Each of these lines is capable of supplying 300 mA AC maximum (170 mA AC
maximum if already connected to the optional valve).
These lines must not be shorted to
any conduit or chassis metal, mis-wired, or connected to any equipment requiring more
than stated maximum allowable current. If these restrictions are not followed, damage
to the CPU PCB will occur.
5.
Use the wire size chart listed when determining the wire size for the control wiring.
Summary of Contents for 9822Q
Page 1: ...Series 9820Q ASTRA Installation Operation Manual MDE 4339 formerly 035090...
Page 18: ...GASBOY Series 9820Q 12 MDE 4339 9820Q ASTRA Installation Operation July 2004...
Page 22: ...GASBOY Series 9820Q 16 MDE 4339 9820Q ASTRA Installation Operation July 2004...
Page 32: ...GASBOY Series 9820Q 26 MDE 4339 9820Q ASTRA Installation Operation July 2004...