background image

12

• Check the controller display and alarm LEDs for sys-

tem malfunction. Reset as required. If the dryer still
won’t start, call your Deltech distributor for assistance.

5.

With the customer-supplied outlet valve and bypass
valve closed, supply compressed air up to the cus-
tomer-supplied inlet valve.

6.

Slowly open the inlet valve, allowing the dryer to reach
operating pressure. Check for air leaks before con-
tinuing.

7.

Slowly open the customer-supplied outlet valve.

8.

Check drain timing - start with 1-2 minute drain off time
and 3-4 second drain on time. Check timing again af-
ter one hour of operation; when drain is activated, noth-
ing but air should drain for one second before the valve
re-closes. Reset timing if necessary, then check after
another hour of operation. Repeat this procedure until
air vents for one second at the end of the drain period.

SHUTDOWN

Energy Saving Cycling dryers are designed to run continu-
ously. Leave the dryer running even if the requirement for
compressed air is not constant — it will not freeze up. A
warm-up period is required if the dryer is disconnected for
more than 60 minutes.

To stop the dryer:

1.

Push the STOP button. If doing any electrical repairs,
disconnect power at customer-supplied power discon-
nect.

2.

Close the customer-supplied shutoff valve downstream
of the dryer.

3.

Close the customer-supplied shutoff valve upstream
of the dryer.

4.

Open the customer-supplied bypass valve, if installed.

5.

Slowly open the customer-supplied blowdown (inter-
nal pressure relief) valve to vent the internal pressure.

6.

Close the blowdown valve when internal pressure is 0
psig.

DANGER

Portions of the control circuit remain energized
when the dryer is off. Disconnect supply power to
the dryer before performing maintenance on the
electrical system.

Restart the dryer according to the start-up instructions.

MAINTENANCE

Energy Saving Cycling dryers require little maintenance for
satisfactory operation. Good dryer performance can be ex-
pected if the following routine maintenance steps are taken.

DANGER

Dismantling or working on any component of the
compressed air system under pressure may cause
equipment failure and serious personal injury. Be-
fore dismantling any part of the dryer or com-
pressed air system, completely vent the internal
pressure to the atmosphere.

General

For continued good performance of your refrigerated dryer,
all refrigeration system maintenance should be performed
by a competent refrigeration mechanic. Before corrective
maintenance is done during the warranty period, call your
local distributor and proceed according to instructions. Re-
fer to the warranty for limits of your coverage.

Daily Maintenance

Check the operation of the automatic drain valve at least
once during each 8-hour shift. Inspect and clean (if neces-
sary) the drain valve strainer. See the Field Service Guide
for remedies to valve malfunctions. See the Controller sec-
tion for timer adjustment.

Dryers with the Energy Management Controller

Check the following front panel lights:

• Power On LED

• High Temperature Alarm LED

• Low Temperature Alarm LED

If either alarm light is lit, shut down the dryer and refer to
the Controller section to determine the cause.

An accurate record of system operating parameters can
aid in troubleshooting, and can indicate gradual reductions
in system efficiency. Using the DISPLAY SELECT button
on the control panel, check the system temperatures, and
record in the Operator’s Log provided in the back of this
manual.

Monthly Maintenance

For air-cooled condensers, inspect the condenser coils.
Remove dust, dirt or other particles with a soft brush or
with compressed air from an OSHA-approved air nozzle
that limits its discharge pressure to 30 psig. If the coils are
coated with oil, grease or other substances that reduce the
cooling efficiency, clean the coils with a solvent. Follow the
solvent manufacturer’s directions for proper use and dis-
posal, including the use of proper protective equipment.

Summary of Contents for RCD800

Page 1: ...050414 CONTENTS INTRODUCTION 2 SAFETY 2 SAFETY INSTRUCTIONS 3 RECEIVING AND INSPECTION 3 INSTALLATION 3 HOW IT WORKS 5 ENERGY MANAGEMENT CONTROLLER EMC 7 EMC MEMBRANE PANEL 8 AUTOMATIC DRAIN VALVES AD...

Page 2: ...der pressure within the dryer can cause severe injury or death 4 High voltage in the motor and control box is danger ous The dryer must be installed in accordance with recognized electrical codes Befo...

Page 3: ...m filing and processing is your responsibility Handling The dryer is mounted on a base to facilitate moving the dryer with a forklift Forks should extend all the way through the forklift channels prov...

Page 4: ...cause a rise in dew point unless the dryer inlet air flow is reduced The refrigerant discharge pressure control will shut down the refrigerant compressor if cooling water is inadequate Table 2 COOLING...

Page 5: ...es CAUTION Operation of dryers with improper line voltage con stitutes abuse and could affect the dryer warranty Standard dryer enclosures and controls are designed to meet NEMA Type 1 electrical stan...

Page 6: ...CUT OUT SWITCH AMBIENT AIRFLOW CONDENSER DISCHARGE COMPRESSOR SUCTION SERVICE ACCESS VALVE HPS GLYCOL TANK GLYCOL MIXTURE SEPARATOR DRAIN SUCTION COMPRESSOR DISCHARGE CONDENSER WATER OUT WATER IN WAT...

Page 7: ...l e D r e y r D e t u n i m 1 o t 0 s d n o c e s 0 6 s e t u n i m 0 6 o t 1 y a l e d o N s t r a t s e r r e y r d y l e t a i d e m m i s r u o h 4 o t 1 s r u o h 4 o t 1 p u m r a w l l i w r e...

Page 8: ...he dryer i e the Dryer On LED is off Up and Down Buttons Used to change the display for the right hand column of LEDs when the DISPLAY SELECT button is pressed These buttons are also used to select th...

Page 9: ...setting the drain open times Drain Closed LED Indicates when the automatic drain valve is closed See Set Auto Drain Off Time Min for information on setting the drain closed times Fahrenheit LED Indic...

Page 10: ...ff time Press the DISPLAY SELECT button until the Set Auto Drain Off Time Min LED is lit The display will show the current drain off time setting in minutes Press the up or down button to increase or...

Page 11: ...rn on at the proper time refer to the Maintenance section of this manual If the dryer is under warranty call your local distributor for authorization before servicing To minimize air losses set the ti...

Page 12: ...equire little maintenance for satisfactory operation Good dryer performance can be ex pected if the following routine maintenance steps are taken DANGER Dismantling or working on any component of the...

Page 13: ...or blow out debris with compressed air from an OSHA approved air nozzle that limits its discharge pressure to 30 psig 12 Check that small port in diaphragm assembly is clear and solenoid coil moves fr...

Page 14: ...I e g r a h e r d n a r i a p e r k a e l e t a c o L y r o t c a f t l u s n o c d e c a l p e r n o i t c u s t n a r e g i r f e R n a h t r e h g i h e r u t a r e p m e t l a m r o n F 0 2 1 n a...

Page 15: ...ype Valve Aids in Disconnecting Compressor from the System PRESSURE GUAGE THERMOMETER DRIP LEG MANOMETER DIFFERENTIAL PRESSURE INDICATOR AUTOMATIC DRAIN VALVE FALSE LOADER Blows Off Air Outside of Com...

Page 16: ...7 2 1 7 0 1 4 6 5 1 2 2 2 3 5 9 7 0 1 2 0 0 2 1 3 7 8 1 5 7 3 7 0 1 8 1 5 2 1 7 8 7 9 5 8 3 5 7 7 1 9 8 9 6 2 7 2 1 7 0 1 8 5 5 6 9 1 2 6 0 0 1 3 2 2 2 NOTE Dimensions and weights are for reference o...

Page 17: ...oltage 460 3 60 Max Min voltage 506 414 Rated Load Amps 7 69 9 62 9 94 Locked Rotor Amps 42 67 80 Minimum Circuit Ampacity 11 69 14 21 14 82 Branch Circuit Fuse Size amps 17 5 20 20 Watts 35 F Evapora...

Page 18: ...18 REPLACEMENT PARTS Air Cooled Models 800 1200 scfm 1 6 7D 7C 9 3 4 5 7A 7B 6 8 2 7A 7B REAR VIEW TOP VIEW FRONT VIEW LEFT SIDE VIEW...

Page 19: ...G 4 0 5 9 9 0 3 G 0 8 5 8 6 0 3 G r o t i c a p a C n u R r o t o M n a F 1 9 0 1 5 0 3 G 1 9 0 1 5 0 3 G 8 5 9 2 6 0 3 G 6 0 6 3 0 6 4 r o s s e r p m o C 0 5 2 6 3 1 3 G 0 4 6 0 1 1 3 G 9 7 1 9 9 0...

Page 20: ...20 REPLACEMENT PARTS Water Cooled Models 800 1200 scfm FRONT VIEW TOP VIEW LEFT SIDE VIEW REAR VIEW 3 1 2 9 5 8 6 4 7D 7C 7A 7B 7A 7B...

Page 21: ...3 G r o t c a t n o C r o s s e r p m o C 9 2 6 6 3 1 3 G 9 2 6 6 3 1 3 G 9 2 6 6 3 1 3 G t i K r e m r o f s n a r T 4 9 3 4 9 0 3 G G 0 8 2 5 6 0 3 9 8 9 0 1 1 3 G y l b m e s s A w o l F r i A A 7...

Page 22: ...SIC TMR 1 2 3 POWER 21 J5 22 20 J4 NO ALARM CONTACTS NO NC GND EMERGENCY STOP SWITCH COMPRESSOR FAN1 1 2 3 HIGH PRESSURE CUT OUT WITH MANUAL RESET HPS M 32 RC DRAIN VALVE RATING 5A 115 VAC 5A 24 VDC 1...

Page 23: ...ER 2 1 IDP DIP SWITCHES 1 2 3 SEE NOTE 14 6 5 8 7 COMPRESSOR 1 1 2 CUTOUT SW J8 2 DRAIN VALVE J7 1 2 3 4 1 2 3 J6 ALARM J5 C OPTION DRAIN VALVE 1 TMR 20 20 3TS 21 2SOL POWER J4 CHASSIS GROUND 5A 24 VD...

Page 24: ...2 2 1 1 2 CONTROLLER 2 1 IDP DIP SWITCHES 1 2 3 SEE NOTE 14 6 5 8 7 COMPRESSOR 1 1 2 CUTOUT SW J8 2 DRAIN VALVE J7 1 2 3 4 1 2 3 J6 ALARM J5 DRAIN VALVE 1 TMR 20 20 3TS 21 2SOL POWER J4 CHASSIS GROUN...

Page 25: ...1 2 4 1 5 3 1 2 4 1 12 12 12 12 6 6 6 4 ENCLOSURE COVER 3091860 8 1 13 T 16 15 14 16 15 14 13 11 17 18 19 20 6 21 21 6 5 9 21 9 11 16 15 14 13 8 2FU2FB 3TS 16 15 14 13 17 18 19 20 6 21 9 23 24 0020244...

Page 26: ...y a l p s i D e t a D e m i T y B n i a r D o t u A e v l a V l i O p m o C l e v e L n O r e w o P h g i H e r u t a r e p m e T m r a l A w o L e r u t a r e p m e T m r a l A s s e c o r P s l o r...

Page 27: ...27 NOTES...

Page 28: ...SLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WAR RANTY OF FITNESS FOR A PARTICULAR PURPOSE THE MANUFACTURER SHALL NOT BE LIABLE FOR LOSS OR DAM AGE BY REASON OF STRICT LIABIL...

Reviews: