![background image](http://html1.mh-extra.com/html/gardner-denver/delcos-3100/delcos-3100_user-manual_3571327016.webp)
1. DELCOS 3100 Electronics
14
1.3.7
[TIMER CONTROL] menu
Danger
The machine can start at any time when programming
in standby mode.
The realtime clock allows you to switch the machine on
and off by means of the timer. In addition, you can specify
a pressure changeover at specific times (e.g. lower level
during the night). Pressure changeover is still active even
if you do not wish to operate in the timer mode [TIMER
CONTROL OFF].
If the system is to be switched on/off by means of the
timer, you must select [TIMER CONTROL ON] from the
[CONTROL MENU] menu and, if necessary, also put the
system into operation (switch on). To set the timer or
pressure changeover, go to the [TIMER CONTROL] menu
option using the and keys. This is where you can
retrieve/select individual parameters using the and
keys.
Basic clock setting:
Example:
[SA 29.01.06 13:55:14] / [SA 01/29/06 13:55:14]
•
Press the key, the week day [SA] flashes
•
Set the day of the week using the and keys
•
Press the key to confirm the new setting
•
The date [29] now flashes
•
Set the date using the and keys
•
Press the key to confirm the new setting
These steps are repeated for setting the month, year,
hours, minutes and seconds. If you confirm the seconds
setting by pressing the key, the clock will start to run
with the new setting.
The process for setting the clock can be cancelled at any
time by pressing the
key.
Setting the timer
You are provided with 7 timer blocks.
Example
Block no. 2, not activated
[2_______ 00:00 00:00]
Example
Block no. 1, system on from Monday to Friday – each
day from 07:30 to 16:15 hours
[1_MTWTF _ 07:30 16:15]
•
Using the and keys, select a timer block, e.g.
block no. 2 [2_______ 00:00 00:00]
•
Press the , the week day flashes (Sunday)
•
Make the setting of your choice using the and
keys
•
Press the key to confirm the new setting
•
The next day of the week (Monday) now flashes
•
Make the setting of your choice using the and
keys
•
Press the key to confirm the new setting
These steps are repeated for the other weekdays and
chosen on and off times.
The process for setting a timer block can be cancelled
at any time by pressing the
key. The old setting is
new restored.
Example 1
For a working time of:
Sunday 22:00 to Saturday 14:00 hrs,
with a daily break from 12:00 to 12:30 hrs, the timer
would have to be set as follows:
[ 1S________ 22:00 24:00]
[ 2_MTWTFS 00:00 12:00]
[ 3_MTWTF_ 12:30 14:00]
[ 4________S 12:30 14:00]
[ 5_________ 00:00 00:00]
[ 6_________ 00:00 00:00]
[ 7_________ 00:00 00:00]
Example 2
You require an uninterrupted supply of compressed air
from:
Monday 6:00 hrs to Friday 22:00 hrs:
[ 1_M______ 06:00 24:00]
[ 2__TWT__ 00:00 24:00]
[ 3______F_ 00:00 22:00]
[ 4________ 00:00 00:00]
[ 5________ 00:00 00:00]
[ 6________ 00:00 00:00]
[ 7________ 00:00 00:00]
Setting pressure changeover
You are provided with a further 7 timer blocks for
changing over to a second pressure range. These are
identified by the
p
2
symbol.