1. DELCOS 3100 Electronics
9
1.3
DELCOS 3100 menu structure (example values)
DELCOS 3100 FS menu structure
(example values)
[MAINTENANCE SCHED.]
TOTAL RUNNING
12345 h
LOADED HOURS
10987 h
AIR FILTER IN
----- h
WATER FILTER IN
9999 h
MOTOR GREASING
9999 h
SHUTDOWN
DEACTIVATED
[CONTROL MENU]
CUT-OUT POINT
10.0 bar / 145 psi
CUT-IN POINT
9.5 bar / 138 psi
AUTOMATIC OPERATION
REMOTE CONTROL
ON
TIMER CONTROL
OFF
AUTO RESTART
OFF
POWER LOSS TIME
2 s
START-UP DELAY
5 s
DRYER PRE-RUN
0 min
RS485-PROTOCOL
ModBus
RS485-BAUDRATE
19200
NUMBER OF SLAVE
1
[FAULT MEMORY]
12! EXT FAULT
11438 h
2! COMP TEMP
9877 h
4 HIGH TEMP
9476 h
18! EM-STOP
4867 h
6! MOTOR TEMP
4310 h
5! MOTOR TEMP
4310 h
2! SENSOR B2
88 h
10! OVER PRESS
17 h
[TIMER CONTROL]
[LIMIT VALUES]
[OPTIONAL INPUTS]
Week day
Date
Time
Saturday
29.01.2006
13:55:14
[SA
01/29/06
13:55:14]
1
_______
00:00 00:00
2
_______
00:00 00:00
3
_______
00:00 00:00
4
_______
00:00 00:00
5
_______
00:00 00:00
6
_______
00:00 00:00
7
_______
00:00 00:00
p
2
1 _______
00:00 00:00
p
2
2 _______
00:00 00:00
p
2
3 _______
00:00 00:00
p
2
4 _______
00:00 00:00
p
2
5 _______
00:00 00:00
p
2
6 _______
00:00 00:00
p
2
7 _______
00:00 00:00
p
2
CUT-OUT POINT 10.0 bar / 145 psi
p
2
CUT-IN POINT
9.5 bar / 138 psi
DESIGN PRESS
10.0 bar / 145 psi
START PROTECT
0.4 bar / 6 psi
HEAVY STARTUP
2.0 bar / 29 psi
FINAL TEMP WARN
59 °C/138 °F
FINAL TEMP MAX
65 °C/149 °F
MIN START TEMP
2 °C/
0
36 °F
RUN-ON TIME
90 s
SOFT STOP
30 s
STAR/DELTA TIME
8 s
SOFTWARE:
HD31V2.00
OPTION 1
DISCH TEMP
OPTION 2
EXT FAULT
OPTION 3
FREE
[BASE LOAD SELECT.] (Option)
[WATER]
OPERATION
OFF
CUT-OUT POINT
10.0 bar / 145 psi
CUT-IN POINT
9.5 bar / 138 psi
BASE LOAD COMP
1
123h K2
K3
K4 k5
k1
CHANGEOVER TIME
24h
QUANT.SLAVES
4
QUANT.RESERVE
0
START DELAY
5s
LOAD NET IN
15min
VOLUME OF NET
20%
CHANGE CYCLE
24h
23h y8 y9 Y10 >-<
SUPPLY MAX.
150s
DRAINAGE MAX.
150s