1. DELCOS 3100 Electronics
13
1.3.3
[FAULT MEMORY] menu
Using the and keys, go to the [FAULT MEMORY]
menu option. This is where you can then retrieve/select
individual entries using the and keys.
Fault messages are stored in the [FAULT MEMORY] in
the following manner, e.g.
12! EXT FAULT
11438 h
2! COMP TEMP
9877 h
4 HIGH TEMP
9476 h
18! EM-STOP
4867 h
6! MOTOR TEMP
4310 h
5! MOTOR TEMP
4310 h
2! SENSOR B2
88 h
10! OVER PRESS
17 h
Shutdowns (faults) are identified with an exclamation mark
(!) whereas warnings appear without the !.
Note
Further information is provided in Chapter 1.4.12, Fault
memory.
The menu closes automatically two minutes after last
pressing a key.
1.3.4
[LIMIT VALUES] menu
Using the and keys, go to the [LIMIT VALUES] menu
option. This is where you can then retrieve/select
individual parameters using the and keys.
The following parameter entries are stored under the
[LIMIT VALUES] menu heading:
DESIGN PRESS 1o.0 bar / 145 psi
START PROTECT
0.4 bar / 6 psi
HEAVY STARTUP 2.0 bar / 29 psi only version FS or RS
EXT. LIMIT
3550 rpm version SR only
FINAL TEMP WARN 59 °C/138 °F
FINAL TEMP MAX
65 °C/149 °F
MIN START TEMP
2 °C/36 °F
RUN-ON TIME
90 s
SOFT STOP
30 s
STAR/DELTA TIME 8 s only version FS or RS
VOL.MAX. =
10.0 m3/min version SR only
VOL.MIN. =
2.0 m3/min version SR only
SOFTWARE:
HD31S2.00
Note
Factory settings cannot be changed by the operator (also
refer to Chapter 1.3.9).
The menu closes automatically two minutes after last
pressing a key
1.3.5
[OPTIONAL INPUTS] menu
The software provides for the [OPTIONAL INPUTS]
menu option. You can have the various additional
monitoring functions included by way of option.
Go to the [OPTIONAL INPUTS] menu option using the
and keys. This is where you can assign three
spare inputs. You merely specify which monitoring
function has been connected to which input. Inputs
declared as [FREE] are not edited/monitored.
You can retrieve/select individual parameters using the
and keys.
An assignment can be selected from the following list
for each input:
Selection
Resident criterion
FREE
Not edited
BEKOMAT FAULT Fault
BEKOMAT WARN. Warning
DRYER FAULT
Fault
DRYER WARNING Warning
EXT FAULT
Fault
EXT WARNING
Warning
DISCH TEMP
Warning
OPERATE_B1
see Chapter 1.7.8
Mot.Lub.System
Warning, only version FS or RS
EXT. RPM LIMIT
SR version only, see Chap. 1.7.4
Example:
OPTION 1
DISCH TEMP
OPTION 2
EXT FAULT
OPTION 3
FREE
The menu closes automatically two minutes after last
pressing a key.
1.3.6
[WATER] menu
Using the and keys, go to the [WATER] menu
option. This is where you can then retrieve/select
individual parameters using the and keys.
The following parameter entries or following values are
stored under the [WATER] menu heading:
CHANGE CYCLE
24h
23h y8 y9 Y10 >-<
SUPPLY MAX.
150s
DRAINAGE MAX.
150s
Note
Further information is provided in Chapter 1.8, Water
circuit.
The menu closes automatically two minutes after last
pressing a key.