2.6 Power Connection
The power requirements for a FPT Gateway are +24VDC @ 330 mA nominal and battery backup
in accordance with local code requirements. For Canadian installation, The FPT Gateway must be
powered by a ULC listed Fire Alarm Control Unit or a ULC listed power supply for fire application
that meets the following specifications. Outside Canada, it can be powered by any power limited
source that is UL listed for use with fire protective signaling units and it meets the following
specifications.
Connect the FPT Gateway’s PC board to the respective power supply connectors through properly
sized conduit.
Figure 2.11 Gateway Power Connection
Table 2.1 Power Supply Specifications
Typical
Min
Max
Input Voltage
+24VDC
+19VDC
+27.6VDC
!
CAUTION:
Disconnect all sources of power before servicing
.
This device and associated equipment may be
damaged by removing and/or inserting cards, modules or interconnecting cables while this unit is
powered
.
This damage may adversely affect the operation of this unit, but its effect may not be readily
apparent.