Device Commands
FPT Gateway Operation
35
FocalPoint™ Gateway Installation & Operation Manual - P/N: 52649:Rev: B3 2/11/10
•
When the gateway receives a silence event for the panel that is not on the network it will
annunciate the panel is silenced on the Workstation, even though the panel is not attached.
•
When the gateway receives a reset event for the panel that is not on the network it will
annunciate the panel has been reset on the Workstation, even though the panel is not attached.
4.3 Device Commands
Workstation commands are sent to a Gamewell/FCI device when the device’s icon is right-clicked
on and a command choice is selected. The following list provides information about some of those
Gamewell/FCI devices commands.
4.4 About FCI Point ID Formats for Off Normal Events
These codes are added to the point ID number displayed when an off normal event occurs for
them. The point’s icon and the event list will both display the appended code.
Table 4.1 Common Gamewell/FCI Device Commands
Panels GW Connects To
Ack
Silence
Reset
Enable/Disable
Comments
7200 Stand Alone
Yes
Yes
Yes
Yes
7100 Stand Alone
No
No
No
No
Monitor Only
7100 on E3 Network
Yes
Yes
Yes
No
Through E3
*
* FPT Gateway must be connected to E3 panel.
E3 Stand Alone and Network
Yes
Yes
Yes
No
NOTE:
For ULC applications, the Internet cannot be used for either primary or ancillary
functionality. When the Internet is used for primary signaling of UL listed applications, the
Workstation is to be used for monitoring purposes only. The Workstation cannot have any control
over the activities of FACPs on the network monitoring system.
Table 4.2 FCI 7200 Point ID Formats for Off Normal Events
ACTION = "AC"
CM SHORT = "CS”
LOOP BREAK = "LB"
TEST FAIL = "TF"
ALARM TEST = "AT"
CROSS ZONE = "CZ"
MISSING = "MI"
TROUBLE = "TR"
ALARM = "AL"
DIRTY = "DY"
OFF-NORMAL = "OF"
UNEXPECTED = "UE"
ALERT = "AR"
DISCONNECT = "DC"
OUTPT FAIL = "OP"
VERIFY = "VE"
ALRM DELAY = "AD"
EXTRA ADDR = "EA"
P.A.S. = "PA"
VERY DIRTY = "VD"
AUD OFFNRM = "AU"
FAULT TEST = "FT"
SPVSN TEST = "ST"
WRONG TYPE = "WT"
Table 4.3 FCI 7100 Point ID Formats for Off Normal Events
ACTION = “AC”
DIRTY = “DY”
MISSING = “MI”
SPVSN TEST = “ST”
ALARM TEST = “AT”
EXTRA ADDR = “EA”
OFF-NORMAL = “OF”
TEST FAIL = “TF”