Gamatronic Electronic Industries Ltd.
User Guide: MEGA V2 SA25, Release 1.5
31
7.
F
IRST
-
TIME SETUP
7.1
Cable connections.
Only an authorized electrician may wire the UPS power connections.
Do not attempt to wire any of the power connections on your own.
To connect the required cables to the UPS:
1.
Ensure that the lines coming into the UPS are equipped with circuit breakers of the
following capacity:
UPS output:
3x40 A Class C
Ac input:
3x40 A Class C
The following table gives the
recommended cable sizes
that must be used when
connecting the UPS. The table states the cable’s cross-sectional area in mm
2
.
If local codes are stricter, they have priority.
Table 5: Recommended cable diameters.
Ac output
Gnd, N, L1, L2, L3
Ac input
Gnd, N, L1, L2, L3
Battery input
6 mm
2
6 mm
2
6 mm
2
(Use the battery cable supplied
by Gamatronic.)