Gamatronic Electronic Industries Ltd.
User Guide: MEGA V2 SA25, Release 1.5
43
8.
Use the
UP/DOWN
button to change the output voltage. You can adjust it in a range
from 220 to 240V. Press
Ent
to apply the change.
After pressing
Ent
the screen looks like this:
9.
The UPS fans may stop working for a moment. They will start up again by themselves
after the voltage adjustment is complete.
10. Press
Esc
to return to the main screen.
8.4
Fine-tune the output voltage
You have the ability to “fine-tune” the UPS output voltage. You can adjust each phase of the
output voltage up and down by one or more volts, if needed.
To change the nominal output voltage:
1.
From the main screen, press the
Ent
button to display the
main menu
.
2.
On the main menu, choose
ADVANCED OPTIONS
and press
Ent
.
3.
In the ADVANCED MENU, select
TECHNICIAN MENU
.
4.
In the TECHNICIAN MENU select
CHANGE VOLTAGE
.
5.
You are prompted to choose the type of voltage to change.
Select
OUTPUT VOLTAGE
.
6.
You are prompted to choose a change to the nominal value or an adjustment (fine-
tuning). Choose
DO ADJUSTMENT
7.
You are prompted to choose the phase to be adjusted. Choose a phase.