Gamatronic Electronic Industries Ltd.
User Guide: MEGA V2 SA25, Release 1.5
23
4.
D
AILY OPERATION
4.1
Power + SA25 start-up
This section explains how to start-up the P
OWER
+
SA after a shutdown.
You are beginning the process from the UPS OFF NO OUTPUT screen.
Figure 20: UPS OFF, no output
1.
Press the ON/OFF button twice.
The BYPASS and ALARM LEDs light up for about 40 seconds.
2.
After a short time the screen reads
“UPS ON, NORMAL MODE”.
The ac INPUT and NORMAL LEDs are lit.
Figure 21: UPS ON, normal mode
3.
You can now turn on the computers or other equipment connected to the UPS.
P
OWER
+
SA start-up is now complete.