The Wiring Regulations
All wiring and installation work shall comply with AS/NZS 3000
Each Fuel Delivery System (FDS) should be protected by a 16 amp circuit breaker that is
capable of being locked off.
When designing the site, cable selections should comply with AS/NZS 3008.1 for Australia
and AS/NZS 3008.2 for New Zealand.
When terminating external cables in the FDS crimp joints should be used and should
comply with AS/NZS 3000.
If the FDS is to be installed at a Marina then all wiring shall be performed in compliance
with AS/NZS 3004