Fulton Boiler FBS Series
5 FBS 01/05
Specifications & Dimensions
Specifications
Model FB-S
1-1.0
1.5-1.0
2-1.0
3-1.0
4-1.0
4-1.25
6-1.25
Nominal steam output T/h
1.0
1.5
2.0
3.0
4.0
4.0
6.0
Operating pressure MPa
1.0
1.0
1.0
1.0
1.0
1.25
1.25
Operating steam temperature
184
184
184
184
184
194
194
Inlet water temperature
20
20
20
20
20
20
20
Water pump electric power (Kw)
2.2
2.2
2.2
3.0
3.0
4.0
5.5
Maximum fuel consumption
Light oil (Kg/h)
60.9
91.4
121.8
182.7
243.6
244.4
365.6
Heavy oil (Kg/h)
62.2
93.3
124.4
186.6
248.8
249.7
374
Natural gas (m
3
/h)
76.6
114.9
153.2
229.8
306.4
315.3
445
Town gas (m
3
/h)
189.4
284.1
378.8
568.2
757.6
778.7
1099.1
Note: 1) All steam output (kg/hr) ratings from 0 MPa at 100 , fuel consumption based on light oil 1,1200 Kcal/kg, heavy oil
10,960 kcal/kg, nature gas 8,900 kcal/m
3
, town gas 3600kcal/m
3
.
2) Specification and dimensions are approximate, the Fulton Companied reserve the right to change specifications or
dimensions.
Connection
Model FB-S
1-1.0
1.5-1.0
2-1.0
3-1.0
4-1.0
4-1.25
6-1.25
Main steam valve
DN50
DN65
DN65
DN100
DN100
DN100
DN125
Safety valve
DN40
DN40
DN40
DN50
DN50
DN50
DN80
Water inlet valve
DN40
DN40
DN40
DN40
DN40
DN40
DN50
Drain valve
DN40
DN40
DN40
DN50
DN50
DN50
DN50
Flue diameter (mm)
300
350
400
450
500
500
600
Water gauge outlet
DN15
DN15
DN15
DN15
DN15
DN15
DN15
Note: 1) The connections of steam valve, safety valve and blow-down valve are all flange connections.
2) If the burners and /or pumps are different, the boiler electrical usages are also different, please based on the finally
drawings.
3) Specifications and dimensions are approximate. The Fulton Companies reserve the right to change specifications
and dimensions.