FULTON FB-S series Installation, Operation & Maintenance Manual Download Page 28

Fulton Boiler FBS Series 

27                                                                            FBS  01/05

 

consulted. Ensure there are no accumulated deposits of sludge in the bottom of the boiler. 

(e)  Remove the feedwater disperser inspect and clean. 
(f)  Replace the man hole and hand hole door gaskets, refer to Section

FITTING NEW GASKET

 

for fitting procedures. 

(g)  Open the boiler front access door with the burner mounted on it as described below. It will be 

necessary to disconnect the gas supply from the gas train and oil supply from the oil lines to allow 

the door to swing open. 

(h)  Where retarders are fitted they should be removed-some burning of the retarders at the inlet end 

is normal. 

(i)  Remove the rear smoke box access doors. 

(j)  Brush through the tubes to remove any deposits from the products of combustion. 

(k)  Using a wire brush, clean the internal surfaces of the furnace and the face of the front tube plate. 

Pay particular attention to the tube ligaments (the spaces between adjacent tubes). 

(l)  Inspect the tube ends for any signs of splitting or burning. These are symptoms of gas reburning 

in the tube ends as a result of poor combustion, e.g. carbon monoxide carry-over. If the tube ends 

exhibit these signs, consult Fulton Boiler Works. 

(m) Clean out the rear smoke boxes to remove the deposits brushed through from the tubes. 

 

IMPORTANT 

Ensure that the rear smoke box drain connections are clean and free from deposits. This is 

particularly  important  on  oil  fired  boilers  because  of  the  acidic  nature  of  the  condensate 

formed. 

 

(p) Inspect the door seal for signs of wear and replace if necessary. The first indication of a worn door 

seal would be evident by signs of leakage around the external periphery of the door. 

WARNING 

When  handling  ceramic  fibre  always  follow  the  local  regulations  regarding  such  materials, 

including the use of breathing apparatus, suitable body protection and protective gloves. 

(q) Examine the internal surface of the door lining for defects. Small repairs may be carried out by 

cutting out the defective area and replacing with new fibre, ensure the correct adhesive is used. 

(r) Examine the end of the burner blast tube where it extends through the door into the furnace. Clean 

off any deposits, paying particular attention to the internal lip where deposits can cause irregular 

flame patterns. 

(s) Inspect the rear smoke box door seals for deterioration and replace if necessary. 

(t) Close the hinged front access door by reversing the opening procedure. 

(u) Re-connect the gas/oil connections. 

(v) Drain and flush the feedwater/ hotwell tank, clean any filters and the strainer in the feedline before 

the pump. 

(w) Drain and flush out the blowdown separator. 

(x) Carry out routine maintenances to the burner as detailed in the manufacturers installation and 

maintenance instructions. 

NOTE 

Depending upon the mode of operation, it may be found that the six monthly interval can be 

extended,  possibly  to  an  annual  service.  It  is  strongly  recommended,  however,  that  the 

interval should be 6 months from initial start up until such times as a ‘pattern of use’ and the 

condition of the boiler after a typical 6 months can be established. 

 

ANNUALLY 

 

It is a requirement of the Factories Act and Pressure Systems Regulations that the boiler is internally 

inspected and re-certified at not more than 14 month intervals. 

It is normal practice to carry out an annual service during which your insurance surveyor would attend 

to carry out the statutory inspection. The scope of a full insurance strip-down is such that it should 

only be attempted by persons competent to do so who have had the necessary training, and have the 

required test equipment. Fulton Boiler Works can offer this service if required. 

The  engineering  surveyor  may  require  the  removal  of  the  ceramic  fibre  insulation  around  the 

periphery of the front tube plate to facilitate inspection of the shell to tube plate weld. The standard 

Fulton  service  kit  includes  replacement  ceramic  fibre  log  material  50*50*150  mm  which  must  be 

glued in place with the adhesive supplied. It is vital the material is fitted ensuring the ends of the fibre 

face into the centre of the boiler. 

Summary of Contents for FB-S series

Page 1: ...FULTON BOILER FB S SERIES INSTALLATION OPERATION MAINTENANCE MANUAL...

Page 2: ...pment the following tests are made to assure the customer the highest standards of manufacturing a Material inspections b Manufacturing process inspections c ASME welding inspection d ASME hydrostatic...

Page 3: ...ney requirements Water supply Valves Electrical Requirements Gas Supply Oil Supply Installation check points Cleaning Boil out of new unit 4 Controls Burner Boiler Control panel Burner 5 Operation Fit...

Page 4: ...be highlighted It is the responsibility and duty of all personnel involved in the operation and maintenance of this equipment to fully understand the WARNINGS CUATIONS and NOTES by which hazards are...

Page 5: ...erating and maintenance instructions are followed FB S boiler is a cylindrical vessel with horizontal tubes passing through and connected to the front and rear tube sheets The vessel contains the wate...

Page 6: ...1 1200 Kcal kg heavy oil 10 960 kcal kg nature gas 8 900 kcal m 3 town gas 3600kcal m 3 2 Specification and dimensions are approximate the Fulton Companied reserve the right to change specifications...

Page 7: ...g Dimensions of the boiler and the necessary clearance Model FB S 1 1 0 1 5 1 0 2 1 0 3 1 0 4 1 0 4 1 25 6 1 25 Total length mm 3324 3624 4072 4772 4956 4956 5540 Total width mm 1705 1785 2100 2196 21...

Page 8: ...by accumulating condensation in flue F The installer should check the draft with a meter at 02 04 W C pressure 0 508 to 1 016mm with the burner off If the pressure is too low a balancing damper should...

Page 9: ...ormation on how to prevent the presence of unwanted solids and corrosive gases Accomplishment of the above objectives generally requires proper feed water treatment before and after introduction of th...

Page 10: ...the burner gas train and furnace while running at full input This pressure is different from the kinds of the burner used for the boiler On FB S1 1 0 to FB S3 1 0 the pressure of supply gas is 50 100...

Page 11: ...inlet should be made using the flexible pipes supplied with the burner C One gate valve should installed to the inlet and outlet of the circulating pump separately A pressure gauge 0 60psi is needed a...

Page 12: ...nd cleaning of the waterside of the pressure vessel should be provided during the course of initial start up The pressure vessel and the steam and return lines or hot water piping represent in effect...

Page 13: ...irring it at all times until the chemical is completely dissolved Add the chemical slowly and in small amounts to prevent excessive heat and turbulence 3 An over flow pipe should be attached to one of...

Page 14: ...e pressure vessel should be drained after being properly cooled to near ambient temperature Hand hole covers should be removed and waterside surfaces should be inspected for corrosion pitting or forma...

Page 15: ...cator when fitted This lamp will illuminate and alarm sound when the water level reaches a pre determined high level The feed pump will stop When the water level falls to the normal working level the...

Page 16: ...with a sensing device to supervise the ignition sequence prove the flame is satisfactory and finally monitor the established flame Should any fault occur either during the ignition sequence or during...

Page 17: ...to preheat the oil to correct temperature The unit is equipped with three thermostats low temperature operating and limit A thermometer and hot oil filter are mounted together as one unit on the top l...

Page 18: ...2 and V3 remain closed for 23 seconds while the minimum side of the gas pressure switch PS checks for an increase in pressure If no crease occurs there is no leakage past V1 and the sequence continues...

Page 19: ...EQUENCE The burner operating sequence begins with a pre purge period on full air Fuel is then supplied to the burner at start rate and ignition initiated Start flame proving is followed by establishme...

Page 20: ...nly Off Burner Pump Switch to the PUMP ONLY position H The feed pump should start and fill the boiler to the pump off level and then switch off NOTE If the 2nd Low Water and High Pressure Alarm Reset...

Page 21: ...intain the internal temperature to a point that the boiler can be simple switched on preferably on low fire and then left to reach working temperature pressure The life expectancy of the boiler and do...

Page 22: ...ter level in the boiler either by evaporation or by opening the main blowdown valve with the key provided c Observe the water level in the water level gauges and check that as the water level reached...

Page 23: ...ed solids level to within the required limits The amount of blowdown and hence time required it dependent on the amount of TDS in the raw water supply the percentage condensate return water treatment...

Page 24: ...d Low Water Alarm Reset switch will extinguish the alarm will cancel and the burner will start NOTE Because the burner shuts down during this test it is possible that the steam load will rapidly decre...

Page 25: ...be within setting of low pressure and light pressure switch d Check burner air proving switch and high fire limit switch e Heavy oil fired unit oil temperature below minimum setting 4 Fuel valve inte...

Page 26: ...nadequate flame signal or open control in the running interlock circuit 7 Interlock device inoperative or defective 8 Air in the oil lines Bleed lines Boiler will not maintain pressure 1 Check oil sup...

Page 27: ...as soon as a leak occurs can prevent costly repairs later Check for signs of leaks on all valves and fittings and take the appropriate action Test all the boiler water level functions by evaporation...

Page 28: ...y cutting out the defective area and replacing with new fibre ensure the correct adhesive is used r Examine the end of the burner blast tube where it extends through the door into the furnace Clean of...

Page 29: ...itting Instructions Blowdown the boiler completely and examine all inspection holes in the boiler If any leakage is evident proceed as follow a Disassembly the crabs and cover plate and remove the ins...

Page 30: ...e boiler instruction manual shipped with your boiler Corrosive acid and chlorine based chemicals in the atmosphere can be damaging to this boiler It is the owner s responsibility to have the boiler ro...

Reviews: