FULTON FB-S series Installation, Operation & Maintenance Manual Download Page 12

Fulton Boiler FBS Series 

11                                                                            FBS  01/05

 

Cleaning 

A

STEAM PIPING 

Steam and water piping systems connected to the boiler may contain oil, grease, or foreign matter. 

The impurities must be removed in order to prevent damage to pressure vessel heating surfaces. On 

a steam system, the condensate should be wasted until tests show the elimination of undesirable 

impurities. During the period that condensate is wasted, attention must be given to the treatment of 

the raw water used as make-up so that an accumulation of unwanted materials or corrosion does not 

occur. For more information, contact your local authorized boiler representative. 

On a hot water system, chemical cleaning is generally necessary and the entire system should be 

drained  after  treatment.  Consult  your  local  authorized  boiler  representative  for  recommendations, 

cleaning compounds, and application procedures. 

B

PRESSURE VESSEL 

The waterside of the pressure vessel must be kept clean from grease, sludge, and foreign material. 

Such  deposits,  if  present,  will  shorten  the  life  of  the  pressure  vessel,  will  interferer  with  efficient 

operation and functioning of control, of safety devices, and quite possibly cause unnecessary and 

expensive re-work, repairs, and down-time. 

The installation and operating conditions that the boiler will be subjected to should be considered and 

cleaning  of  the  waterside  of  the  pressure  vessel  should  be  provided  during  the  course  of  initial 

start-up. 

The pressure vessel and the steam and return lines or hot water piping represent, in effect, a closed 

system. Although the steam and return (condensate) lines or hot water piping system may have been 

previously cleaned, it is possible that: 

(1) Cleaning has been inadequate. 

(2) Partial or total old system is involved. 

(3) Conditions may prevent adequate cleaning of piping. 

The pressure vessel waterside should be inspected on a periodic basis. An inspection will reveal true 

internal  conditions  and  serve  as  a  check  against  conditions  indicated  by  chemical analysis  of  the 

boiler water. Inspection should be made three months after initial starting and at regular 6-, 9-, or 

12-month  intervals  thereafter.  The  frequency  of  further  periodic  inspections  will  depend  upon  the 

internal conditions found. 

If  any  unwanted  conditions  are  observed,  contact  your  local  authorized  boiler  representative  for 

recommendations. 

Any sludge, mud or sediment found will need to be flushed out. If excessive mud or sludge is noticed 

during the blowdown the scheduling or frequency of blowdown may need to be revised. The need for 

periodic draining or washout will also be indicated. 

Any oil or grease present on the heating surfaces should be removed promptly by a boil-out with an 

alkaline detergent solution. 

NOTE 

Temperature  of  initial  fill  of  water  for  hydrostatic  tests,  Boil-out,  or  for  normal  operation 

should be as stated in the ASME Boiler Code. 

 

 

Summary of Contents for FB-S series

Page 1: ...FULTON BOILER FB S SERIES INSTALLATION OPERATION MAINTENANCE MANUAL...

Page 2: ...pment the following tests are made to assure the customer the highest standards of manufacturing a Material inspections b Manufacturing process inspections c ASME welding inspection d ASME hydrostatic...

Page 3: ...ney requirements Water supply Valves Electrical Requirements Gas Supply Oil Supply Installation check points Cleaning Boil out of new unit 4 Controls Burner Boiler Control panel Burner 5 Operation Fit...

Page 4: ...be highlighted It is the responsibility and duty of all personnel involved in the operation and maintenance of this equipment to fully understand the WARNINGS CUATIONS and NOTES by which hazards are...

Page 5: ...erating and maintenance instructions are followed FB S boiler is a cylindrical vessel with horizontal tubes passing through and connected to the front and rear tube sheets The vessel contains the wate...

Page 6: ...1 1200 Kcal kg heavy oil 10 960 kcal kg nature gas 8 900 kcal m 3 town gas 3600kcal m 3 2 Specification and dimensions are approximate the Fulton Companied reserve the right to change specifications...

Page 7: ...g Dimensions of the boiler and the necessary clearance Model FB S 1 1 0 1 5 1 0 2 1 0 3 1 0 4 1 0 4 1 25 6 1 25 Total length mm 3324 3624 4072 4772 4956 4956 5540 Total width mm 1705 1785 2100 2196 21...

Page 8: ...by accumulating condensation in flue F The installer should check the draft with a meter at 02 04 W C pressure 0 508 to 1 016mm with the burner off If the pressure is too low a balancing damper should...

Page 9: ...ormation on how to prevent the presence of unwanted solids and corrosive gases Accomplishment of the above objectives generally requires proper feed water treatment before and after introduction of th...

Page 10: ...the burner gas train and furnace while running at full input This pressure is different from the kinds of the burner used for the boiler On FB S1 1 0 to FB S3 1 0 the pressure of supply gas is 50 100...

Page 11: ...inlet should be made using the flexible pipes supplied with the burner C One gate valve should installed to the inlet and outlet of the circulating pump separately A pressure gauge 0 60psi is needed a...

Page 12: ...nd cleaning of the waterside of the pressure vessel should be provided during the course of initial start up The pressure vessel and the steam and return lines or hot water piping represent in effect...

Page 13: ...irring it at all times until the chemical is completely dissolved Add the chemical slowly and in small amounts to prevent excessive heat and turbulence 3 An over flow pipe should be attached to one of...

Page 14: ...e pressure vessel should be drained after being properly cooled to near ambient temperature Hand hole covers should be removed and waterside surfaces should be inspected for corrosion pitting or forma...

Page 15: ...cator when fitted This lamp will illuminate and alarm sound when the water level reaches a pre determined high level The feed pump will stop When the water level falls to the normal working level the...

Page 16: ...with a sensing device to supervise the ignition sequence prove the flame is satisfactory and finally monitor the established flame Should any fault occur either during the ignition sequence or during...

Page 17: ...to preheat the oil to correct temperature The unit is equipped with three thermostats low temperature operating and limit A thermometer and hot oil filter are mounted together as one unit on the top l...

Page 18: ...2 and V3 remain closed for 23 seconds while the minimum side of the gas pressure switch PS checks for an increase in pressure If no crease occurs there is no leakage past V1 and the sequence continues...

Page 19: ...EQUENCE The burner operating sequence begins with a pre purge period on full air Fuel is then supplied to the burner at start rate and ignition initiated Start flame proving is followed by establishme...

Page 20: ...nly Off Burner Pump Switch to the PUMP ONLY position H The feed pump should start and fill the boiler to the pump off level and then switch off NOTE If the 2nd Low Water and High Pressure Alarm Reset...

Page 21: ...intain the internal temperature to a point that the boiler can be simple switched on preferably on low fire and then left to reach working temperature pressure The life expectancy of the boiler and do...

Page 22: ...ter level in the boiler either by evaporation or by opening the main blowdown valve with the key provided c Observe the water level in the water level gauges and check that as the water level reached...

Page 23: ...ed solids level to within the required limits The amount of blowdown and hence time required it dependent on the amount of TDS in the raw water supply the percentage condensate return water treatment...

Page 24: ...d Low Water Alarm Reset switch will extinguish the alarm will cancel and the burner will start NOTE Because the burner shuts down during this test it is possible that the steam load will rapidly decre...

Page 25: ...be within setting of low pressure and light pressure switch d Check burner air proving switch and high fire limit switch e Heavy oil fired unit oil temperature below minimum setting 4 Fuel valve inte...

Page 26: ...nadequate flame signal or open control in the running interlock circuit 7 Interlock device inoperative or defective 8 Air in the oil lines Bleed lines Boiler will not maintain pressure 1 Check oil sup...

Page 27: ...as soon as a leak occurs can prevent costly repairs later Check for signs of leaks on all valves and fittings and take the appropriate action Test all the boiler water level functions by evaporation...

Page 28: ...y cutting out the defective area and replacing with new fibre ensure the correct adhesive is used r Examine the end of the burner blast tube where it extends through the door into the furnace Clean of...

Page 29: ...itting Instructions Blowdown the boiler completely and examine all inspection holes in the boiler If any leakage is evident proceed as follow a Disassembly the crabs and cover plate and remove the ins...

Page 30: ...e boiler instruction manual shipped with your boiler Corrosive acid and chlorine based chemicals in the atmosphere can be damaging to this boiler It is the owner s responsibility to have the boiler ro...

Reviews: