- 13 -
Clear 5: Hydraulic Unit Heat exchanger thermistor error
Hydraulic Unit LED:
Green 4 fl ashes / Red 2 fl ashes
Outdoor Unit LED:
22 fl ashes
Probable causes:
• Misconnection.
• Sensor failure.
• Interface PCB failure.
Check:
1. Check the sensor connection:
-
See if the connector has been removed
-
See if the connection is correct
-
Check for any damage on the sensor cable.
After solving the misconnection problem, switch the heat pump back on.
2. Remove the sensor and check its resistance value :
- Check the resistance value.
Temperature (°C) 0 5 10 15 20 25 30 35 40 45 50
Resistance (k ) 176 134 103 80,3 62,9 49,7 39,6 31,7 25,6 20,8 17,1
- If the thermistor is faulty, replace it.
OK
3. Check the electronic board voltage:
- Make sure circuit diagram of hydraulic unit and check terminal voltage at thermistor
(DC5.0V)
- If there is no voltage, replace Interface PCB.
OK
Gray
Gray
Black
Waterstage / Maintenance Manual / 2105 - EN