Clear 18: Fan motor error (permanent stoppage)
Hydraulic Unit LED:
Green 9 fl ashes / Red 7 fl ashes
Outdoor Unit LED:
16 fl ashes (fan 1), 17 fl ashes (fan 2)
Probable causes:
• Fan motor failure.
• Motor protection.
• Main PCB failure.
Check:
1. Check fan rotation:
- Switch off the heat pump and rotate the fan manually.
- If the fan or bearings are faulty, replace them.
2. Check the ambient temperature around the motor:
- Check excessively high temperature around the fan.
Wait until the temperature comes down again and switch the
fan back on.
3. Check the main board output voltage:
- On the outdoor unit, check the output voltage (DC) of the following connectors:
Terminals
Voltage
1 (red)/ 3 (black)
300
390V
4 (white)/3 (black)
15 ±2V
If the voltage is incorrect, replace Main PCB.
OK
OK
FAN MOTOR
1
(UPPER)
FAN MOTOR
2
(LOWER)
CN802
CN803