- 84 -
▼ Confi guration Functions
When an installation is started up, the hydraulic diagram
presetting for that installation must be entered.
Presettings
Line Nr
Programming line
5700
Pre-setting
Only Pre-setting 1 to 4 are used among 9 availables.
Heating circuits/Cooling Circuit
Line Nr
Programming line
5710
Heating circuit 1
5711
Cooling circuit 1
(Off / 4-pipe system / 2-pipe system)
5715
Heating circuit 2
Heating circuit 1
Using this setting, heating circuit 1 can be switched on
and off .
Cooling circuit 1
• Off
The cooling circuit is deactivated.
• 4-pipe system
Not compatible with the Waterstage heat pump.
This setting relates to passive cooling.
• 2-pipe system
Activates the heat pump cooling mode. However,
the cooling kit must have been previously connected.
Warning
If the cooling kit has not been connected and the cooling
mode is activated the heat pump will behave abnormally
and might cause some unwanted discomfort.
Information
Switching on the cooling mode causes the menu
"Cooling circuit 1" to appear.
Heating circuit 2
Using this setting, heating circuit 2 can be switched on
and off .
DHW
Line Nr
Programming line
5731
DHW ctrl elem Q3
• No charging request
No DHW charging via Q3.
• Charging pump
DHW charging is eff ected with a pump connected to
terminal Q3.
• Diverting valve
DHW charging is eff ected with a diverting valve
connected to terminal Q3.
Electric backup
Line Nr
Programming line
5806
Type el imm heater fl ow
Within the type of electric backup, 4 settings are possible :
• 3-stage
Not used.
• 2-stage excuding
Not used.
• 2-stage complementary
The backup 1 starts alone, then the backup 2 starts
alone, then the two backups start simultaneously.
Exemple for a 3kw backup and a 6kw backup,
1st stage : 3kw, 2nd stage : 6kw, 3rd stage : 3+6=9kw.
• Modulating Ux
The backup 1 is regulated as required.
Basic unit EX/E
Line Nr
Programming line
5981
Cont type input EX1, EX2, EX3
5983
5985
The type of contact can be selected:
• NC
The input’s function is active when voltage is not present.
• NO
The input’s function is active when voltage is present.
The descriptions relating to the functions of the EX
contact apply when an NO contact is selected.
Waterstage / Maintenance Manual / 2105 - EN