Water may flow out of the outdoor unit when it is
operating. Do not install the unit on a paved terrace;
choose a well-drained location (e.g. gravel or sand).
If installation is carried out in an area where the
temperature stays below 0°C for long periods, check
that the presence of ice does not present any danger.
A drainage pipe can also be connected to the outdoor
unit (see
fig. 14
).
• Nothing should obstruct the air circulation through the
evaporator and out from the fan (
fig. 13
).
•
Keep the outdoor unit away from heat sources and
flammable products.
• Make sure that the unit does not disturb the
surrounding area or inhabitants (noise level, draught,
low temperature of the ejected air freezing the plants
in its path).
fig. 13 -
Minimum installation clearances around the outdoor unit (all models)
B
E
G
G
D
BB
A
G
B
B
H
A
B
D
E
G
B
F
J
B
B
K
E
F
H
B
B
B
B
H
E
D
H
B
B
H
B
B
D
B
B
H
E
A
≥
80 mm
B
≥
100 mm
C
≥
200 mm
D
≥
300 mm
E
≥
500 mm
F
≥
600 mm
G
≥
1000 mm
H
≥
1500 mm
J
≥
2000 mm
K
≥
3000 mm
►
Installation of the outdoor unit
▼
Installation precautions
The outdoor unit must only be installed
outside. If a shelter is required, it must have
broad openings on all 4 sides and installation
clearances must be observed.
• Choose the location of the appliance after discussion
with the client.
• We recommend choosing a site that is sunny but
sheltered from strong cold prevailing winds.
• The unit must be easily accessible for future installation
and maintenance work (
page 20
).
• Ensure that connections to the hydraulic unit can be
made easily.
• The outdoor unit is able to withstand bad weather but
avoid installing it in a position where it is likely to be
exposed to significant dirt or flowing water (under a
defective gutter for example).
Waterstage / Installation / 2011 - EN