- 58 -
Line
Function
Setting range
or display
Setting
increment
Basic
setting
Heat pump (HP)
2803
S
Overrun time cond pump
8... 240 s
1 s
240s
2843
S
Compressor off time min
0... 120 min
1 min
8 min
2844
S
Switch-off temp max
8... 100 °C
1 °C
75 °C
2862
S
Locking time stage 2 / mod
0... 40 min
1 min
5 min
2873
S
Compressor mod run time
10... 600 s
1 s
240 s
2882
S
Release integr electric flow
0... 500 °Cmin
1 °Cmin
100 °Cmin
2884
S
Release el flow below OT
Electrical release - start-up with outdoor
temperature
-30... 30 °C
2 °C
2899
I
Min flow switch consumers
1...1200 l/h
1 l/h
600
l/h
2916
S
Max setpoint HP DHW charg
8... 80 °C
60 °C
2920
S
With electrical utility lock (EX1)
Locked (Blocked on standby),
Released
Released
Released
: HP = ON _ Back-up DHW = off _ 1st back-up HP = off _ 2nd back-up HP = off _ Boiler = ON
Locked (Blocked on standby)
: HP = off _ Back-up DHW = off _ 1st back-up HP = off _ 2nd back-up HP = off _
Boiler = ON
Energy meter
3095 --> 3110 : Not used
3113
U
Energy brought in
Kwh
--
Cumulation of total consumed electrical energy.
Electrical energy consumed = Electrical energy absorbed by outdoor unit + electric energy absorbed by the heating
electrical backup and / or DHW electrical backup (if installed).
3121 --> 3123 : Not used
3124
U
Energy brought in heating 1 (N - 1)
Kwh
--
3125
U
Energy brought in DHW 1
Kwh
--
3126
U
Energy brought in cooling 1
Kwh
--
3128 --> 3130 : Not used
3131
U
Energy brought in heating 2 (N - 2)
Kwh
--
3132
U
Energy brought in DHW 2
Kwh
--
3133
U
Energy brought in cooling 2
Kwh
--
3135 --> 3137 : Not used
3138
U
Energy brought in heating 3 (N - 3)
Kwh
--
3139
U
Energy brought in DHW 3
Kwh
--
3140
U
Energy brought in cooling 3
Kwh
--
3142 --> 3144 : Not used
3145
U
Energy brought in heating 4 (N - 4)
Kwh
--
3146
U
Energy brought in DHW 4
Kwh
--
3147
U
Energy brought in cooling 4
Kwh
--
3149 --> 3151 : Not used
3152
U
Energy brought in heating 5 (N - 5)
Kwh
--
3153
U
Energy brought in DHW 5
Kwh
--
3154
U
Energy brought in cooling 5
Kwh
--
Waterstage / Installation / 2011 - EN