- 82 -
►
Settings sheet
Setting
Description
Set to.
Menus
Preliminary settings
20
language
operator
section
1
hour / minutes
time & date
2
day / month
time & date
3
year
time & date
5700
installation config.
configuration
Heating circuit No. 1
if 2 circuits = the least warm one (e.g.: floor)
710
comfort setpoint
HC1 adjust.
712
reduced setpoint
HC1 adjust.
720
heating curve slope
HC1 adjust.
741
flow temp setpoint max
HC1 adjust.
750
room influence
HC1 adjust.
790 / 791
optimis. at switch-on / off
HC1 adjust.
834
servomotor travel time
HC1 adjust.
850 / 851
floor drying
HC1 adjust.
Heating circuit No. 2 (with 2
nd
circuit option)
= the warmest one (e.g.: radiators)
1010
comfort setpoint
HC2 adjust.
1012
reduced setpoint
HC2 adjust.
1020
heating curve slope
HC2 adjust.
1041
flow temp setpoint max
HC2 adjust.
1050
room influence
HC2 adjust.
1090 / 1091 optimis. at switch-on / off
HC2 adjust.
1134
servomotor travel time
HC2 adjust.
1150 / 1151
floor drying
HC2 adjust.
Domestic Hot Water (with DHW kit)
1610
nominal DHW temp. setpoint
DHW
1612
reduced DWH temp. setpoint
DHW
1620
DHW release
DHW
1640 to 1642 legionella cycle
DHW
5024
DHW switch-on differ.
DHW tank
5030
charging time limitation
DHW tank
5061
heater release
DHW tank
Setting
Description
Set to.
Menus
Boiler backup
3700
OT.switch-on authoris.
addit. gen.
3705
swith-off delay
addit. gen.
Miscellaneous
6420
input H33 function
1
configuration
6100
OT sensor correction
configuration
6120
frost protection on/off
configuration
6205
reset settings
configuration
6220
software version
configuration
6711
reset heat pump
error
Cooling
5711
cooling unit
2 pipes
configuration
Faults (if a fault occurs, press"Info" key)
No. 10
outdoor sensor
No. 33
flow temp. sensor
No. 44
return temp. sensor
No. 50
DHW temp. sensor
No. 60
room sensor 1
No. 65
room sensor 2
No. 105
maintenance message
No. 121
HC1 flow T not reached
No. 122
HC2 flow T not reached
No. 127
leg. prot. T not reached
No. 369
external fault (EX3)
No. 370
outdoor unit connect error
6711
reset heat pump
error
Heat pump
2844
switch-off temp max
heat pump
2884
OT auth. to start elec. aux.
heat pump
2920
Pk day clear (EX1) rel / lock
heat pump
Swimming pool (with "swimming pool" kit)
2056
generator setpoint
Sw pool
Outdoor unit faults (see page 75)
Waterstage / Installation / 2011 - EN
Summary of Contents for Waterstage WOYK150LJL
Page 17: ... ...
Page 37: ... ...
Page 39: ... 39 fig 33 Cable passages Power cables Sensor cables Waterstage Installation 2011 EN ...
Page 67: ... ...