Push the four latches inward.
▶
Carefully place the LC heat sink onto the CPU socket.
▶
Push the four latches outward.
Figure 152: Installing the LC heat sink (B)
▶
Fasten the four captive screws in the sequence printed on the LC heat sink
(1 to 4).
Tool: Torx T30 screw driver
Torque: 0.9 - 1.0 Nm
▶
Proceed for the second LC heat sink in the same way.
▶
Remove the orange protective caps from the tube connectors.
Liquid cooling (LC)
GX2570 M6
Upgrade and Maintenance Manual
203