Important information
Before starting up
●
During installation and before operating the server enclosure, observe the
instructions on environmental conditions for your server enclosure.
●
If the server enclosure is brought in from a cold environment, condensation
may form both inside and on the outside of the server enclosure.
Wait until the server enclosure has acclimatized to room temperature and is
absolutely dry before starting it up. Material damage may be caused to the
server enclosure if this requirement is not observed.
●
Only transport the server enclosure in its original packaging or in packaging
that protects it from impacts and jolts.
In Japan and APAC, transporting the server enclosure in its original
packaging does not apply.
Installation and operation
●
This server enclosure should not be operated in ambient temperatures
above 35 °C. For server enclosures with Advanced Thermal Design the
ambient temperature can increase to 40 °C or 45 °C.
●
If the server enclosure is integrated into an installation that draws power
from an industrial power supply network with an IEC309 connector, the
power supply's fuse protection must comply with the requirements for non-
industrial power supply networks for type A connectors.
●
The server enclosure automatically adjusts itself to a mains voltage, see the
type label of your server enclosure. Ensure that the local mains voltage lies
within these limits.
●
This server enclosure must only be connected to properly grounded power
outlets or connected to the grounded rack internal power distribution server
enclosure with tested and approved power cords.
●
Ensure that the server enclosure is connected to a properly grounded power
outlet close to the server enclosure.
●
Ensure that the power sockets on the server enclosure and the properly
grounded power outlets are easily accessible.
●
The On/Off button or the main power switch (if present) does not isolate the
server enclosure from the mains power supply. In case of repair or servicing
disconnect the server enclosure completely from the mains power supply,
unplug all power plugs from the properly grounded power outlets.
Summary of Contents for PRIMERGY CX400 M4
Page 6: ...Operating Manual CX400 M4 ...
Page 10: ...10 Operating Manual CX400 M4 Introduction ...
Page 14: ...14 Operating Manual CX400 M4 Before you start ...
Page 42: ...42 Operating Manual CX400 M4 Important information ...
Page 74: ...74 Operating Manual CX400 M4 Operation ...
Page 82: ...82 Operating Manual CX400 M4 Technical data ...
Page 84: ...84 Bearbeitungsstand Bestellnummer Warranty and service ...