2-36. E: A5. Low pressure error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
10 time flash
Timer indicator
5 time flash
Economy indicator
Continuous flash
Error code
E: A5
outdoor unit
Refer to “Error code table (Outdoor unit: for 34 model
only)” on page 1
Detective actuator
Outdoor unit main PCB
Protection stop by suction pressure ≥ 0.02 MPaG
continued 5 minutes repeats 5 times within 24 hours.
Suction pressure sensor
Forecast of cause
3-way valve not opened
Outdoor unit ambient temperature too low
Outdoor unit operation failure, foreign matter on heat
exchanger
EEV defective, strainer clogged
Solenoid valve defective
Low pressure sensor characteristics defective
Insufficient refrigerant
Main PCB failure
Check point 1. Check if 3-way valve is open
If the 3-way valve is closed, open the 3-way valve and check operation.
NOTE:
For cooling operation, check gas side of the 3-way valve.
For heating operation, check liquid side of the 3-way valve.
↓
Check point 2. Check the outdoor unit ambient temperature (Only when heating operation)
Outdoor unit ambient temperature lower than operating range?
↓
Check point 3. Check the outdoor unit fan and heat exchanger (Only when heating operation)
•
No foreign object in air passage?
•
Heat exchanger fins clogged?
•
Fan rotes?
•
Check the motor. (Refer to outdoor unit fan motor in
↓
Check point 4. Check the electronic expansion valve (EEV) and strainer
•
Check if EEV open.
Refer to outdoor unit Electronic Expansion Valve (EEV) in
•
Check the strainer clogging.
↓
Check point 5. Check the suction pressure sensor
Check the suction pressure sensor characteristics.
NOTE:
For the characteristics of the thermistor, refer to suction pressure sensor in
↓
2-36. E: A5. Low pressure error (Outdoor unit)
- (03-54) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AOTG30KMTC
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2019 06 27 SR_CH01_AS004EF_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 05 12 SR_CH02_AS004EF_05 ...
Page 35: ...3 TROUBLESHOOTING 2020 05 08 SR_CH03_AS004EF_02 ...
Page 38: ......
Page 128: ...6 2 Outdoor unit 03 90 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 129: ...4 CONTROL AND FUNCTIONS 2020 05 08 SR_CH04_AS004EF_02 ...
Page 132: ......
Page 163: ...5 FILED WORKING 2019 07 24 SR_CH05_AS004EF_01 ...