
7-8. Compressor preheating
By preheating the compressor, warm airflow is quickly discharged when the operation is started.
•
Triggering condition 1
– Outdoor temperature ≤ 20°C
When outdoor temperature reaches following degrees, compressor preheating stops.
30 model
25°C
34 model
26°C
– 30 minutes after compressor stopped
•
Triggering condition 2
0°C
Off
On
Tn
Tn
2°C
Tn: Outdoor unit heat exchanger temp.
7-9. Electronic expansion valve control
The most proper opening of the electronic expansion valve is calculated and controlled under the
present operating condition based on the table below.
Operation mode
Pulse range
Cooling/dry mode
Between 32 and 480 pulses
Heating mode
Between 45 and 480 pulses
NOTE:
At the time of supplying the power to the outdoor unit, the initialization of the electronic ex-
pansion valve is operated (528 pulses are input to the closing direction).
7-10. Prevention to restart for 3 minutes (3 minutes st)
Compressor won’t enter operation status for 140 seconds after compressor is stopped, even if any
operation is given.
7-8. Compressor preheating
- (04-22) -
7. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for AOTG30KMTC
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2019 06 27 SR_CH01_AS004EF_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 05 12 SR_CH02_AS004EF_05 ...
Page 35: ...3 TROUBLESHOOTING 2020 05 08 SR_CH03_AS004EF_02 ...
Page 38: ......
Page 128: ...6 2 Outdoor unit 03 90 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 129: ...4 CONTROL AND FUNCTIONS 2020 05 08 SR_CH04_AS004EF_02 ...
Page 132: ......
Page 163: ...5 FILED WORKING 2019 07 24 SR_CH05_AS004EF_01 ...