7-14. Peak cut operation (for 34 model)
The current value is limited to reduce the power consumption by external input.
Peak cut level
Level 1
Level 2
Level 3
Level 4
Peak cut for rated capacity
Forced thermostat
off
50%
75%
100%
NOTES:
• During defrost operation, peak cut operation becomes invalid.
• Even during the peak cut operation, the operations of current overload, economy, and low noise
are effective and the outdoor unit operates by lowest current of them.
7-15. Outdoor unit low noise operation (for 34 model)
The compressor frequency and outdoor unit fan speed are limited to reduce the operation noise by
external input.
Low noise mode
Outdoor fan speed
Compressor
frequency
Sound level
rpm
rps
dB (A)
Level 1
Cooling/Dry
690
43
-2
Heating
690
49
Level 2
Cooling/Dry
690
30
-4
Heating
690
36
NOTES:
• During the defrost operation, the compressor operates by the speed for defrost operation.
• Even during the low noise operation, the operations of current overload, economy, and peak cut
are effective and the outdoor unit operates by lowest current of them.
Capacity priority mode
• Operation condition
The function setting is set to 1.
• Capacity check condition
– Shortage: Compressor frequency > limited compressor frequency for low noise mode
– Enough: Compressor frequency ≤ limited compressor frequency for low noise mode
• Operation
When detecting the shortage capacity or enough capacity condition continuous 30 minutes, the
mode is changed as follows:
– Automatic switching 1 (Level 1 setting)
Enough for 30 min
Shortage for 30 min
Normal operation
Low noise mode 1
– Automatic switching 2 (Level 2 setting)
Low noise
mode 2
Normal
operation
Low noise
mode 1
Enough for 30 min
Shortage for 30 min
Enough for 30 min
Shortage for 30 min
7-14. Peak cut operation (for 34 model)
- (04-25) -
7. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for AOTG30KMTC
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2019 06 27 SR_CH01_AS004EF_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 05 12 SR_CH02_AS004EF_05 ...
Page 35: ...3 TROUBLESHOOTING 2020 05 08 SR_CH03_AS004EF_02 ...
Page 38: ......
Page 128: ...6 2 Outdoor unit 03 90 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 129: ...4 CONTROL AND FUNCTIONS 2020 05 08 SR_CH04_AS004EF_02 ...
Page 132: ......
Page 163: ...5 FILED WORKING 2019 07 24 SR_CH05_AS004EF_01 ...