Peak cut mode
By performing following on-site work, operation that suppresses the current value can be enabled:
The air conditioner is set to the “Peak cut mode” when closing the contact input of a commercial
timer or on/off switch to a connector on the control PCB of the outdoor unit.
•
Circuit diagram example
Outdoor unit
control PCB
Connected unit
Example: Switch
Connector
1
2
Signal
Locally purchased
*10 m
•
Contact capacity: DC 24 V or more, 10 mA or more.
•
*: Make the distance from the PCB to the connected
unit within 10 m.
•
Construct a circuit as shown in this figure with using
optional parts mentioned below.
•
Input signal: On in “Peak cut mode”
•
Input signal: Off in normal operation
•
To set the level of “Peak cut mode”, refer to
On
Off
On
Off
Input signal
Peak cut mode
•
Optional part
Part name
Model name
Exterior
External connect kit
UTY-XWZXZ3
External input wire
4-1. External input
- (05-33) -
4. External input and output (For outdoor unit: AOTG34KMTC only)
FIELD
WORKING
FIELD
WORKING